INSTALLER SETTING
140

Water cooling set temp.

Determine cooling setting temperature range when water temperature is selected as setting
temperature.
• In the installer setting list, select water cooling set temp category, and press [OK] button to
move to the detail screen.
OK
Value
Max.
FCU use
Min.
FCU Not use
h Value is in °C
h When set to inlet temperature, the default value of Min. temp is set to the minimum value that
can be set.
NOTE
Water condensation on the floor
• While cooling operation, it is very important to keep leaving water temperature higher than
16 °C. Otherwise, dew condensation can be occurred on the floor.
• If floor is in humid environment, do not set leaving water temperature below 18 °C.
NOTE
Water condensation on the radiator
• While cooling operation, cold water may not flow to the radiator. If cold water enters to the
radiator, dew generation on the surface of the radiator can be occurred.
OK
Default
Outlet
24
22~27
5
5~20
16
16~20
Range
Inlet
22~27
10~20
20