Forced Cooling Operation - LG MULTI F Installation Manual

Multi-zone heat pump systems
Hide thumbs Also See for MULTI F:
Table of Contents

Advertisement

Function
18/24(1Ø) kBtu/h
DIP-SW
54(1Ø) kBtu/h

Forced Cooling Operation

Adding the refrigerant in winter.
Setting Procedure
1. Set the Dip Switch as follow after shutting the power source down.
2. Reset the power.
3. Check that the Red LED of PCB is on during work. (The indoor unit is operated by force.)
4 Add the specific amount of refrigerant.
CAUTION
• When the green LED of PCB is on, compressor is going to be off because
of low pressure.
• You should return the Dip Switch to operate normally after finishing the
operation.
48 Multi Air Conditioner
36(1Ø) kBtu/h
SW01N

Hide quick links:

Advertisement

Table of Contents

Troubleshooting

loading

This manual is also suitable for:

Multi f maxLmu18chvLmu24chvLmu30chvLmu36chvPmbd3620 ... Show all

Table of Contents