Step
3. Remove the drain pump.
1
Cut the clamp (A) and
remove the drain hose.
2
Remove the 3 screws,
and then the drain
pump.
4. Remove the thermistors.
1
Cut the 2 clamps (A)
and remove the heat
insulation.
2
Cut the clamp (B).
3
Pull out the liquid pipe
thermistor.
4
Cut the clamp (C).
5
Remove the heat
insulation and pull out
the middle thermistor.
Removal Procedure
Procedure
Clamp (B)
Drain hose
Liquid pipe
thermistor
Clamp (C)
Middle thermistor
Thermistors / Drain Pump / Float Switch
Drain pump
Clamp (B)
Clamp (A)
(R25890)
Clamp (A)
(R25891)
Points
 You may cut the 2 clamps
(B) for easy access to the
screws.
 When removing the
thermistor, remove the drain
pump beforehand.
 Liquid pipe thermistor layout
Liquid pipe
thermistor
Clamp
(A)
Clamp (B)
 Be careful not to lose the clip
of the thermistor.
Clip
(R25899)
(R25900)
(R25935)