BT000F/020F/060F/080F
Mechanical installation
MOUNTING
BRACKET
Wiring Diagrams
Models BT000F & 020F
3 wire / 2 position
(ON-OFF)
3 wire / 3 point floating
PC Board
Terminal
1
2
3
4
Stroke adjustment
To adjust the stroke, press and release the reset button to start the auto-stroke process. The LED should be illuminated.
First option:
The actuator will then travel in both directions to find it's limit.
The LED will extinguish, the process is complete.
Second option:
When the desired end position is reached, press and release the reset button. The actuator will now return back to its
origin position. (you can also press and release the reset button when It's reaches the origin position)
The LED will extinguish, the process is complete.
CLUTCH
BBT1060A
Reset button
Dip switch
LED
ON
1 2 3
Specification & Installation instruction
Manually close the damper blades and positioned the
1.
actuator at 0º or 90º.
Slide the actuator onto the shaft.
2.
Tighten the nuts on the "U" bolt to the shaft with a 8mm
3.
wrench to a torque of 60 in.lb. [6,7 Nm].
Slide the mounting bracket under the actuator. Ensure free
4.
movement of the slot at the base of the actuator. The
bracket pin must be placed in the mid distance of the slot.
Fix the bracket to the ductwork with #8 self-tapping screws.
5.
Models BT060F & 080F
2 wire / 2 position
(ON-OFF)
4 wire / 3 point floating
Dip switch settings
ON
1
2
3
Rotation: CW
Fail safe return at 0º
Not used
Rotation: CCW
Fail safe return at 90º
Not used
ON
1
2
3
2