Universal Room Controller AROB Series BACnet Communication Module User Guide AROB24T (Temperature sensor) AROB24TH (Temperature and Humidity sensors) AROB24TGH (Temperature, Humidity, and CO2 sensors) AROB24TGVH (Temperature, Humidity, VOC, and CO2 sensors) AROB-BACnet Guide_170920...
The controller provides a BACnet network interface between BACnet client devices and Neptronic Controller series devices. It uses the BACnet Master Slave/Token Passing (MS/TP) protocol at the BACnet MAC layer.
For more information, refer to the MAC Address and Max_Master section. Name of Configure the name of the device through the WriteProperty service to Device Device Object.Object_Name the device Object.Object_Name. For example, ARO24TGVH. www.neptronic.com Page | 2 ...
MAC addresses is high. Therefore, each unit must poll four units until it finds the right one to pass the token. Example 3 MAC=0, Max_Master=1 MAC=2, Max_Master=2 www.neptronic.com Page | 3 ...
Cold Reset: The Cold Reset restarts the controller with Factory configuration. Warning: The Cold Reset erases the actual configuration when setting the MSTP address. Therefore, exercise caution while performing a Cold Reset. www.neptronic.com Page | 4 ...
Out_of_Service Property Neptronic controllers offer the use of the Out_of_Service writable property. When the value of this property is set to True, it disconnects the object from the physical input, enabling you to input other values. This is useful for special applications or while troubleshooting.
Status value that represents the modulation percentage of analog output 2 Present Value AO.2 Status AO.2 based on demand. Status AO.2 is only available for App Profile, 0 = No Profile 0% to 100%, Resolution 1% Relinquish Default (manual configuration). www.neptronic.com Page | 7 ...
0 to 1,000 PPB, Resolution 1 PPB functioning VOC sensor installed. Represents the outdoor temperature. Only appears if MSV.18 is set to OAT AV.14 Status Outdoor Temp level Out_of_Service -40°F to 257°F or -40°C to 125°C, Resolution 0.2°F/0.1°C Sensor. www.neptronic.com Page | 8 ...
Page 11
0 Volts to 10 Volts (0 Volts to AV.34), Resolution 0.1 Volt The minimum value is restricted by the maximum value. In other words, the Present Value minimum value should be less than the maximum value configured in AV.34. www.neptronic.com Page | 9 ...
Page 12
Cfg BO1 Low OAT Lockout Present Value Resolution 0.2°F/0.1°C connected to AI1 is lower than the value set here, the output will remain at its normal state (default: open). Only appears if MSV.18 is set to OAT Sensor. www.neptronic.com Page | 10 ...
Page 13
3.6°F to 90°F or 2°C to 50°C, Resolution 0.2°F/0.1°C Present Value cooling ramp. Configuration value that represents the time for cooling integral factor AV.61 Cfg Cooling I Time 1 to 120 seconds, Resolution 1 second Present Value compensation. www.neptronic.com Page | 11 ...
Page 14
Cfg Dehumidification Setpoint min restricted by the maximum dehumidification setpoint value. 0% RH to 100% RH (0% RH to AV.79), Resolution 0.1% Present Value The Cfg Dehumidification Setpoint min requires a functioning humidity sensor installed. www.neptronic.com Page | 12 ...
Page 15
Status value that represents the analog output 2 in millivolts. Status AO 2 m V AV.94 Status AO 2 m V 0 to 10,000 millivolts, Resolution 1mV Read Only is only available for App Profile, 0 = No Profile (manual configuration). www.neptronic.com Page | 13 ...
Represents the status value to inform if the OAT lockout alarm is active for the BV.4 Status BO 1 OAT Lockout binary output 1. (0) No, (1) Yes Read Only 0 = No, 1 = Yes Only appears if MSV.18 is set to OAT Sensor. www.neptronic.com Page | 14 ...
Page 17
Represents the status of the heating command for Analog Output 1. (0) No, (1) BV.23 Cfg Heating Command AO 1 Yes If you select No Profile as the App Profile, the Cfg Heating Command AO 0 = No, 1 = Yes Present Value 1 becomes writable. www.neptronic.com Page | 15 ...
Page 18
The Cfg CO 2 Command AO 2: BV.33 Cfg CO 2 Command AO 2 Present Value 0 = No, 1 = Yes Only available for App Profile, 0 = No Profile (manual configuration). Requires a functioning CO2 sensor installed. www.neptronic.com Page | 16 ...
Page 19
Represents the status of the dehumidification command for Binary Output 2. (0) BV.45 Cfg Dehumidification Command BO 2 No, (1) Yes Present Value 0 = No, 1 = Yes The Cfg Dehumidification Command BO 2 is only available for App Profile, www.neptronic.com Page | 17 ...
Off: Controller does not respond to any demand. Dehumidification MSV.3 User Humidity system mode Present Value Dehumidification: Controller activates dehumidification. Auto Auto: Controller activates the Auto mode, enabling dehumidification and Humidification humidification as per demand. Humidification: Controller activates humidification. www.neptronic.com Page | 18 ...
Page 21
Direct Mode: The signal ramp is configured from minimum to maximum, for Direct mode MSV.14 Cfg AO 1 DA/RA Mode Present Value example 0 to 10Vdc. Reverse Mode Reverse Mode: The signal ramp is configured from maximum to minimum, for example 10 to 0Vdc. www.neptronic.com Page | 19 ...
Page 22
MSV.23 Cfg Application Profile Installation and Operation Manual. Present Value Temp Only No Profile: Controller allows manual configuration (For advanced users). Temp, RH, and CO2 Temp Only: Outside Air Applications Temp, RH, and CO2: Conference Room Application www.neptronic.com Page | 20 ...
Page 23
Status Relay 2 is only available for App Profile, 0 = No Profile (manual configuration). MSV.29 Status Relay 2 Read Only Off: The contact state has not been initialized. Reset Set: The contact of the relay is closed. Reset: The contact of the relay is open. www.neptronic.com Page | 21 ...