Neptronic AROB24T User Manual

Neptronic AROB24T User Manual

Universal room controller. arob series bacnet communication module

Advertisement

Quick Links

 
 
Universal Room Controller
AROB Series
BACnet Communication Module User Guide
AROB24T (Temperature sensor)
AROB24TH (Temperature and Humidity sensors)
AROB24TGH (Temperature, Humidity, and CO2 sensors)
AROB24TGVH (Temperature, Humidity, VOC, and CO2 sensors)
 
 
AROB-BACnet Guide_170920

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the AROB24T and is the answer not in the manual?

Questions and answers

Summary of Contents for Neptronic AROB24T

  • Page 1     Universal Room Controller AROB Series BACnet Communication Module User Guide AROB24T (Temperature sensor) AROB24TH (Temperature and Humidity sensors) AROB24TGH (Temperature, Humidity, and CO2 sensors) AROB24TGVH (Temperature, Humidity, VOC, and CO2 sensors)     AROB-BACnet Guide_170920...
  • Page 2: Table Of Contents

    Object Table Information  ..............................  7   Analog Input (AI) ................................  7   Analog Output (AO)................................  7   Analog Value (AV) ................................  8   Binary Input (BI) ................................  1 4  Binary Output (BO)  ...............................  1 4  Binary Value (BV) .................................  1 4  Multi State Value (MSV)  ...............................  1 8  Notes ....................................  2 2      www.neptronic.com Page | i  ...
  • Page 3: Introduction

    The controller provides a BACnet network interface between BACnet client devices and Neptronic Controller series devices. It uses the BACnet Master Slave/Token Passing (MS/TP) protocol at the BACnet MAC layer.
  • Page 4: Bacnet Properties Configuration

    For more information, refer to the MAC Address and Max_Master section. Name of  Configure the name of the device through the WriteProperty service to Device Device Object.Object_Name the device Object.Object_Name. For example, ARO24TGVH.       www.neptronic.com Page | 2  ...
  • Page 5: Configuration Options

    MAC addresses is high. Therefore, each unit must poll four units until it finds the right one to pass the token. Example 3  MAC=0, Max_Master=1  MAC=2, Max_Master=2 www.neptronic.com Page | 3  ...
  • Page 6: Network Reset

    Cold Reset: The Cold Reset restarts the controller with Factory configuration. Warning: The Cold Reset erases the actual configuration when setting the MSTP address. Therefore, exercise caution while performing a Cold Reset.       www.neptronic.com Page | 4  ...
  • Page 7: Device Object Properties

    AROB24TGVH, programmable up to 32 Bytes Description Programmable up to 32 Bytes (default: BACnet Unit Controller) Object_Type Device System_Status Operational Vendor_Identifier Always 153 Vendor_Name Always Neptronic Model_Name Example, ARBGVH Firmware_Revision currently, 1.06 Application_Software_Version currently, 1.27 Protocol_Version Always 1 Protocol_Revision Always 14 DataBase_Revision Default 0;...
  • Page 8: Object Types Supported

    Out_of_Service Property Neptronic controllers offer the use of the Out_of_Service writable property. When the value of this property is set to True, it disconnects the object from the physical input, enabling you to input other values. This is useful for special applications or while troubleshooting.
  • Page 9: Object Table Information

    Status value that represents the modulation percentage of analog output 2 Present Value AO.2 Status AO.2 based on demand. Status AO.2 is only available for App Profile, 0 = No Profile 0% to 100%, Resolution 1% Relinquish Default (manual configuration).     www.neptronic.com Page | 7  ...
  • Page 10: Analog Value (Av)

    0 to 1,000 PPB, Resolution 1 PPB functioning VOC sensor installed. Represents the outdoor temperature. Only appears if MSV.18 is set to OAT AV.14 Status Outdoor Temp level Out_of_Service -40°F to 257°F or -40°C to 125°C, Resolution 0.2°F/0.1°C Sensor. www.neptronic.com Page | 8  ...
  • Page 11 0 Volts to 10 Volts (0 Volts to AV.34), Resolution 0.1 Volt The minimum value is restricted by the maximum value. In other words, the Present Value minimum value should be less than the maximum value configured in AV.34. www.neptronic.com Page | 9  ...
  • Page 12 Cfg BO1 Low OAT Lockout Present Value Resolution 0.2°F/0.1°C connected to AI1 is lower than the value set here, the output will remain at its normal state (default: open). Only appears if MSV.18 is set to OAT Sensor. www.neptronic.com Page | 10  ...
  • Page 13 3.6°F to 90°F or 2°C to 50°C, Resolution 0.2°F/0.1°C Present Value cooling ramp. Configuration value that represents the time for cooling integral factor AV.61 Cfg Cooling I Time 1 to 120 seconds, Resolution 1 second Present Value compensation. www.neptronic.com Page | 11  ...
  • Page 14 Cfg Dehumidification Setpoint min restricted by the maximum dehumidification setpoint value. 0% RH to 100% RH (0% RH to AV.79), Resolution 0.1% Present Value The Cfg Dehumidification Setpoint min requires a functioning humidity sensor installed. www.neptronic.com Page | 12  ...
  • Page 15 Status value that represents the analog output 2 in millivolts. Status AO 2 m V AV.94 Status AO 2 m V 0 to 10,000 millivolts, Resolution 1mV Read Only is only available for App Profile, 0 = No Profile (manual configuration).   www.neptronic.com Page | 13  ...
  • Page 16: Binary Input

    Represents the status value to inform if the OAT lockout alarm is active for the BV.4 Status BO 1 OAT Lockout binary output 1. (0) No, (1) Yes Read Only 0 = No, 1 = Yes Only appears if MSV.18 is set to OAT Sensor. www.neptronic.com Page | 14  ...
  • Page 17 Represents the status of the heating command for Analog Output 1. (0) No, (1) BV.23 Cfg Heating Command AO 1 Yes If you select No Profile as the App Profile, the Cfg Heating Command AO 0 = No, 1 = Yes Present Value 1 becomes writable. www.neptronic.com Page | 15  ...
  • Page 18 The Cfg CO 2 Command AO 2: BV.33 Cfg CO 2 Command AO 2 Present Value 0 = No, 1 = Yes  Only available for App Profile, 0 = No Profile (manual configuration).  Requires a functioning CO2 sensor installed. www.neptronic.com Page | 16  ...
  • Page 19 Represents the status of the dehumidification command for Binary Output 2. (0) BV.45 Cfg Dehumidification Command BO 2 No, (1) Yes Present Value 0 = No, 1 = Yes  The Cfg Dehumidification Command BO 2 is only available for App Profile, www.neptronic.com Page | 17  ...
  • Page 20: Multi State Value (Msv)

    Off: Controller does not respond to any demand. Dehumidification MSV.3 User Humidity system mode Present Value Dehumidification: Controller activates dehumidification. Auto Auto: Controller activates the Auto mode, enabling dehumidification and Humidification humidification as per demand. Humidification: Controller activates humidification. www.neptronic.com Page | 18  ...
  • Page 21 Direct Mode: The signal ramp is configured from minimum to maximum, for Direct mode MSV.14 Cfg AO 1 DA/RA Mode Present Value example 0 to 10Vdc. Reverse Mode Reverse Mode: The signal ramp is configured from maximum to minimum, for example 10 to 0Vdc. www.neptronic.com Page | 19  ...
  • Page 22 MSV.23 Cfg Application Profile Installation and Operation Manual. Present Value Temp Only No Profile: Controller allows manual configuration (For advanced users). Temp, RH, and CO2 Temp Only: Outside Air Applications Temp, RH, and CO2: Conference Room Application www.neptronic.com Page | 20  ...
  • Page 23 Status Relay 2 is only available for App Profile, 0 = No Profile (manual configuration). MSV.29 Status Relay 2 Read Only Off: The contact state has not been initialized. Reset Set: The contact of the relay is closed. Reset: The contact of the relay is open.   www.neptronic.com Page | 21  ...
  • Page 24: Notes

    Notes     400 Lebeau Blvd, Montreal, Qc, H4N 1R6, Canada www.neptronic.com Toll-free in North America: 1-800-361-2308 Tel.: (514) 333-1433 Fax: (514) 333-3163 Customer service fax: (514) 333-1091 Monday to Friday: 8:00am to 5:00pm (Eastern time)    ...

This manual is also suitable for:

Arob24thArob24tgvhArob24tgh

Table of Contents