Download Print this page
Neptronic BT000F Specification & Installation Instructions

Neptronic BT000F Specification & Installation Instructions

Advertisement

Quick Links

Technical Data
Fail safe - Enerdrive
Power consumption
Control signal
Auxiliary switches
Ingress protection
Running time through
90º
Torque
Power supply
Electrical connection
Inlet bushing
Angle of rotation
Direction of rotation
Ambient temperature
Storage temperature
Relative Humidity
Weight
Warning: Do not press the clutch when actuator is powered
Dimensions
Caution
We strongly recommend that all neptronic® products be wired to a separate transformer and that transformer shall service only neptronic® products. This precaution will
prevent interference with, and/or possible damage to incompatible equipment.
When multiple actuators are wired on a single transformer, polarity must be observed. Long wiring runs create voltage drop which may affect the actuator performance.
1
Enerdrive System U.S.A. Patent #5,278,454
BTF-210802
Feature:
• Mounts easy on round
& square shaft (with option –8).
• External clutch for manual adjustments.
• Maintenance free.
• Position indicator.
• Fail safe by Enerdrive System
(on model 060 & 080).
• Auxiliary switches
(on model 020 & 080).
BT000F
BBTF1000A
No
15 VA
3 wire / 2 position,
3 wire / 3 point floating
4 wire / 3 point floating
No
IP22 equivalent to Nema type 2,
IP54 equivalent to Nema type 3R if water tight inlet
bushings (not supplied NEP617) are installed
0 to 90 degrees, mechanically adjustable (factory set with 90º stroke)
Reversible, Clockwise (CW) or Counterclockwise (CCW) (factory set with CW direction)
Specification & Installation instructions
1
BT060F
BBTF1060A
Yes
24VA Peak, 15VA
2 wire / 2 position,
3 wire / 2 position,
3 wire / 3 point floating
6 to 8 sec Torque dependant
50 in.lb. [5,6 Nm] at rated voltage
22 to 26 VAC or 28 to 32 VDC
2
18 AWG [0.8 mm
] minimum
2 inlet bushing of 13/16 in [20.6 mm]
-22ºF to +122ºF [-30ºC to +50ºC]
-22ºF to +122ºF [-30ºC to +50ºC]
5 to 95 % non condensing.
3 lbs. [1.4 kg]
Dimension
A
B
C
model 000 & 060
D
model 020 & 080
Actuator
Old Number
BBTF1000A
BBTF1021A
BBTF1060A
BBTF1080A
BT020F
BBTF1021A
BBTF1080A
No
15 VA
24VA Peak, 15VA
2 wire / 2 position,
4 wire / 3 point floating
Yes (2)
IP22 equivalent to Nema type 2
Inches
Metric (mm)
1.50
3.64
6.60
3.02
3.81
BT000F
BT020F
BT060F
BT080F
BT080F
Yes
38.1
92.5
167.5
76.8
96.8
1

Advertisement

loading

Summary of Contents for Neptronic BT000F

  • Page 1 96.8 Caution We strongly recommend that all neptronic® products be wired to a separate transformer and that transformer shall service only neptronic® products. This precaution will prevent interference with, and/or possible damage to incompatible equipment. When multiple actuators are wired on a single transformer, polarity must be observed. Long wiring runs create voltage drop which may affect the actuator performance.
  • Page 2 Fix the bracket to the ductwork with #8 self-tapping screws. Wiring Diagrams Models BT000F & 020F Models BT060F & 080F 3 wire / 2 position 2 wire / 2 position...

This manual is also suitable for:

Bt060fBt020fBt080fBbtf1000aBbtf1060aBbtf1021a ... Show all