Daikin Emura 3 Series Service Manual page 67

Table of Contents

Advertisement

To check if the refrigerant field piping is compliant with the regulations
5.2.2 Repair procedures
To open the stop valves of the refrigerant circuit
RXJ20~50A + FTXJ-A(W)(S)(B)
Split Emura 3 R32
ESIE22-04 – 2022.04
Is the pressure in the refrigerant circuit
correct?
Yes
No
1 Check if the refrigerant field piping is compliant with the regulations. Adjust as
needed. See installation manual for field piping specifications.
Is the problem solved?
Yes
No
Prerequisite: Remove the required plate work, see
1 Remove the caps.
a Liquid stop valve
b Gas stop valve
2 Completely open the stop valves by screwing the stop valve screw
counterclockwise.
Is the problem solved?
Yes
No
5
|
Third party components
Action
Return to the troubleshooting of the
specific error and continue with the
next procedure.
Replace the leaking part of the
refrigerant circuit, see
4
procedures" [
 67].
Action
No further actions required.
Return to the troubleshooting of the
specific error and continue with the
next procedure.
"4.1 Plate
a
b
Action
No further actions required.
Return to the troubleshooting of the
specific error and continue with the
next procedure.
draft – 22/04/2022 08:50
"5.2.2 Repair
4
work" [
 48].
Service manual
67