Daikin Emura 3 Series Service Manual page 38

Table of Contents

Advertisement

3
|
Troubleshooting
3.5.34 UA-00 – Indoor unit, outdoor unit mismatching problem
3.5.35 UH-00 – Malfunction of system
Service manual
38
draft – 22/04/2022 08:50
INFORMATION
If all procedures listed above have been performed and the problem is still present,
contact the helpdesk.
Trigger
Signal transmission
between outdoor and
indoor unit abnormality.
Improper combination of
outdoor and indoor unit.
To solve the error code
INFORMATION
It is recommended to perform the checks in the listed order.
1 Check for improper combination of the indoor unit and the outdoor unit. See
the combination table in the Databook for more information.
2 Perform a check of the power supply, connections, wiring,... between the
outdoor unit and the indoor unit. See
Possible cause: Faulty wiring between the outdoor unit and the indoor unit.
3 Perform a check of the main PCB. See Main PCB.
Possible cause: Faulty main PCB.
4 Perform a check of the indoor unit main PCB. See Indoor unit PCB.
Possible cause: Faulty indoor unit main PCB.
5 Perform a check of the indoor unit power PCB. See Indoor unit power PCB.
Possible cause: Faulty indoor unit power PCB.
INFORMATION
If all procedures listed above have been performed and the problem is still present,
contact the helpdesk.
Trigger
In case of connection with
multi indoor units, when
error UA, U0 or A5 occurs
in other indoor unit.
To solve the error code
INFORMATION
It is recommended to perform the checks in the listed order.
1 Check all other indoor units for the following error codes. If found, see
"3.5 Error based
troubleshooting" [
Effect
Unit will stop operating.
"5.1 Electrical
Effect
Unit will stop operating.
4
 15] to solve the specific error.
Reset
Power reset via outdoor
unit.
4
circuit" [
 60].
Reset
Auto reset.
RXJ20~50A + FTXJ-A(W)(S)(B)
Split Emura 3 R32