▪ A subset of the latest technical data is available on the regional 9 Commissioning Daikin website (publicly accessible). Checklist before commissioning..........10 ▪ The full set of latest technical data is available on the Daikin To perform a test run..............10 Business Portal (authentication required). 9.2.1 To perform a test run using the wireless remote control .................
▪ the accessory bag located at the bottom of the package, ▪ the mounting plate attached to the back of the indoor unit, ▪ the spare SSID sticker located on the front grille. FTXJ-A(W)(S)(B) Installation manual Daikin room air conditioner 3P482320-16X – 2021.12...
(minimum 10 mm INFORMATION thickness, polyethylene foam). ▪ Daikin Industries Czech Republic s.r.o. declares that ▪ Wall strength. Check whether the wall or the floor is strong the radio equipment type inside of this unit is in enough to support the weight of the unit.
1 Bore a 65 mm large feed-through hole in the wall with a Putty downward slope towards the outside. Wall hole cover 2 Insert a wall embedded pipe into the hole. FTXJ-A(W)(S)(B) Installation manual Daikin room air conditioner 3P482320-16X – 2021.12...
2 Gradually pour approximately 1 l of water in the drain pan, and check for water leaks. Right-side piping Right-bottom piping Right-back piping Remove the pipe port cover here for right side piping Remove the pipe port cover here for right-bottom piping Installation manual FTXJ-A(W)(S)(B) Daikin room air conditioner 3P482320-16X – 2021.12...
If the temperature is higher than 30°C and the humidity is higher than RH 80%, the thickness of the insulation materials should be at least 20 mm to prevent condensation on the surface of the insulation. FTXJ-A(W)(S)(B) Installation manual Daikin room air conditioner 3P482320-16X – 2021.12...
Transmission wiring and power supply wiring may cross, but may NOT run parallel. ▪ In order to avoid any electrical interference the distance between both wirings should ALWAYS be at least 50 mm. Installation manual FTXJ-A(W)(S)(B) Daikin room air conditioner 3P482320-16X – 2021.12...
4 Secure the indoor unit to the mounting plate using 2 indoor unit fixing screws M4×12L (accessory). 2× Drain hose Interconnection cable FTXJ-A(W)(S)(B) Installation manual Daikin room air conditioner 3P482320-16X – 2021.12...
Prerequisite: Test run should be performed in accordance with the commissioning checklist is also available on the Daikin operation manual of the indoor unit to make sure that all functions Business Portal (authentication required).
▪ A subset of the latest technical data is available on the regional Daikin website (publicly accessible). 11.1 Solving problems based on error ▪ The full set of latest technical data is available on the Daikin codes Business Portal (authentication required). Fault diagnosis by the wireless remote control 13.1...
Need help?
Do you have a question about the FTXJ25A2V1BW and is the answer not in the manual?