en – Original Instructions
5.4 Control panel installation
NOTE:
Do not install the control panel high above the ground, to avoid areas where the air
temperature may exceed 40°C (104°C): risk of overheating.
Respect the operating limits of chapter 12.
Depending on the pump set model, the control panel can be installed on the fuel tank, or
detached. To install the control panel on the wall:
1. Remove the control panel from the tank by removing the screws.
2. Install the control panel:
3. Secure the control panel to the wall with bolts:
98
• Near the pump set
• In an accessible location.
• Appropriate
• Suitable for the support material and the application conditions.
Take into account the dimensions and centre distances of the holes shown in the figure.
235 mm
(9.25 in)
314 mm (12.36 in)
GEMK – Fire-fighting Pump Set