Checks Before Starting The Pump Set; System And Installation Room; Pump Set And Hydraulic Components - Xylem GEMK Installation, Operation And Maintenance Instructions

Fire-fighting pump set
Table of Contents

Advertisement

Available languages

Available languages

3. Press:
4. When setting a text parameter, press:
5. Press  to store the set value and return to the submenu.
6. Press STOP to save and exit the setting section.
Note: If no buttons are pressed for more than 2 minutes, the display returns to the main page
and the parameters are not saved.

8.4 Checks before starting the pump set

Carry out the checks and operations described below after one of the following events:
• The first installation
• A general overhaul
• Extraordinary maintenance
• A period of inactivity.

8.4.1 System and installation room

Check:
• The status of the system and the room
• That there are no objects near the air duct openings
• That the exhaust gas evacuation system is correctly connected to the motor
• The status of the drain pump and the floor water detector with alarm if present
• The status of the devices used for ensuring the minimum and maximum room temperature.

8.4.2 Pump set and hydraulic components

Check:
• The grounding of the pump set and the control panel
• The presence and status of the anti-vibration dampers
• The anchoring to the floor
• The status of the piping system connections
• The presence and correct assembly of the anti-vibration joints
• That the tie rods of the discharge anti-vibration joint are disassembled
• The correct assembly and precharge of the diaphragm tanks, if required
• The calibration of the 2 start pressure switches
• The tightening of all bolts
• That there are no leaks.
GEMK – Fire-fighting Pump Set
1.
Selected parameter
2.
Graph bar
3.
Minimum value
4.
Set value
5.
Maximum value
6.
Factory settings
• ◄ or ► to increase or decrease the value
• ◄ + ▲ to set the minimum value
• ▲ + ► to set the maximum value
• ◄ + ► to return to the factory settings.
• ▲ or ▼ to select letters and numbers
• ◄ or ► to move the cursor within the text
• ▲ + ▼ to select the letter A.
en – Original Instructions