Bosch CLC6101i-W 50 HE Service Manual page 24

Air/air heat pump
Table of Contents

Advertisement

Climate Class 6100i / 6000i / 8100i / 8000i
Item
Mode
Outside air tem-
Auto
perature
thermistor
(TH3)
Cooling
Dehumidifying
Heating
Suction pipe
Cooling
thermistor
Dehumidifying
(TH4)
Heating
2-way valve
Cooling
thermistor
Dehumidifying
(TH5)
Heating
When resistance is
Control opera-
low (temperature
tion
judged higher than
actual)
Operation mode
Cooling mode is
judgment
activated even if room
temperature is low.
Operation not
Normal operation.
affected
Rating control
Defrosting operation is
Defrosting
activated unnecessari-
ly.
Expansion valve
Compressor operates,
control
but room does not be-
come cool (expansion
valve is open).
Expansion valve
Compressor operates,
control
but room does not be-
come warm (expansion
valve is open).
Expansion valve
Frost accumulates on
control
indoor unit evaporator
and room does not be-
come cool (expansion
valve is closed).
Operation not
Normal operation.
affected
Short-circuit
Outdoor unit
thermistor
short-circuit error
indication.
Outdoor unit
thermistor
short-circuit error
indication.
Outdoor unit
thermistor
short-circuit error
indication.
Outdoor unit
thermistor
short-circuit error
indication.
Outdoor unit
thermistor
short-circuit error
indication.
Outdoor unit
thermistor
short-circuit error
indication.
Outdoor unit
thermistor
short-circuit error
indication.
4-4
When resistance is
high (temperature
Open-circuit
judged lower than
actual)
Heating mode is ac-
Outdoor unit therm-
tivated even if room
istor open-circuit
temperature is high.
error indication.
Normal operation.
Outdoor unit therm-
istor open-circuit
error indication.
Defrosting operation
Outdoor unit therm-
is not activated, and
istor open-circuit
frost accumulates
error indication.
on outdoor unit.
Frost accumulates
Outdoor unit therm-
on evaporator inlet
istor open-circuit
section, and room
error indication.
does not become
cool (expansion
valve is closed).
Frost accumulates
Outdoor unit therm-
on expansion valve
istor open-circuit
outlet section,
error indication.
and room does
not become warm
(expansion valve is
closed).
Compressor oper-
Outdoor unit therm-
ates, but room does
istor open-circuit
not become cool
error indication.
(expansion valve is
open).
Normal operation.
Outdoor unit therm-
istor open-circuit
error indication.