4. Electrical connection

4.1

Connecting the power supply

4.1.1

Notes on electrical installation

When performing the electrical installation, it is important to
observe all valid national and regional regulations as well as
the provisions of the responsible electrical supply company.
The electrical installation must only be carried out by a qual-
ified electrician who is responsible for compliance with the
existing standards and regulations.
4.1.2

Connection data

The connected voltage and frequency must correspond to
the values stated on the rating plate.
The electrical installation and any repairs may only be carried
out by authorised specialist personnel.
Use only original spare parts!
Install the pre-fuse cited in the Technical Specifications (cir-
cuit-breaker or slow fuse) to protect from short-circuits.
If several fans are operated on a single pre-fuse, observe the
total connected load.
The roof-mounted fan must be connected to the mains via
an all-pole disconnecting device to overvoltage category III
(IEC 61058-1).
4.1.3

Overvoltage protection and supply line load

The unit does not have its own overvoltage protection.
Measures must be taken at the supply end by the switch-
gear manufacturer or operator to ensure effective protection
against lightning and overvoltage.
The units are classified as overvoltage category III. The mains
voltage must not exceed a tolerance of ±10%.
4.1.4

PE conductor connection

The PE conductor must be connected to the PE conductor
system of the overall system.
4.1.5

Installing the power supply

Remove the mains connector from the packaging and con-
nect to the mains as shown in the connection diagram.
The connection terminal supplied allows the connection of
cable cross-sections of 0.5 to 4 mm².
A smaller pilot wire (section 4.2) may be selected (min. 0.34
mm²).
In accordance with NFPA 70 (NEC), only copper conduc-
tors must be used to connect the supply cable to the mains
connector.
If no wire end ferrules are used, strip the individual wires by
max. 9 mm (observe the applicable clearances and creepage
distances).
Connect the connector to the roof-mounted fan from below.
12
Connection
Pin
L
N
PE
+10 V
1
0...10 V/PWM
2
GND
3
Speed
4
Tab. 2:
Connection designations
Function/assignment
Power supply
Neutral conductor
PE conductor
Voltage output 10 V max. 1.1 A,
galvanically isolated, not short
circuit-protected
Control input 0...10 V or PWM,
galvanically isolated, impedance
100 kΩ
GND connection of the control
interface
Speed output Open Collector, 1
pulse per revolution, galvanically
isolated
Rittal roof-mounted fan