Assembly and connections
– This is either 15 mm measured between drilling tem-
EN
plates or between the associated mounting cut-outs
in accordance with the following table:
Model No.
3237.xxx
3238.xxx
3239.xxx
3240.xxx
3243.xxx
Tab. 2:
Separation between two mounting cut-outs
4.2.2

Layout of the components in the enclosure

Observe the air flows from the internal fans of installed
electronic components. For installation, it is important
to ensure that the airflows of fans and built-in electronic
components do not have a negative influence on one
another (air short-circuit). The corresponding minimum
distances between the fan and component must be
observed in order to ensure unhindered air circulation.
4.3
Fitting the fan-and-filter unit or outlet
filter
The fan-and-filter unit or outlet filter is mounted on a
vertical panel of the enclosure:
◾ For this purpose, the appropriate door, side or rear
panel must be cut out using the supplied drilling
template.
The fan-and-filter unit is generally fitted in the lower part
of the enclosure, and the outlet filter in the upper part.
4.3.1

Cutting out the enclosure

◾ Stick the self-adhesive drilling template supplied to
the envisaged position on the door, side or rear panel
of the enclosure.
Lines indicating the dimensions of cut-outs and drilling
specifications for mounting and fixing of the fan (only
necessary for sheet metal thickness 2.5 mm and
above) are to be found on the drilling template. See
also fig. 10 and fig. 11, page 15.
Risk of injury!
Carefully deburr all cut-outs to prevent
injuries caused by sharp edges.
◾ Make the cut-outs including the line width as per the
drilling template.
Deburr the cut-outs.
4.3.2

Fitting the fan-and-filter unit

– The fan may be fitted without tools, by simply snap-
ping into the preconfigured mounting cut-out.
– Make sure that the clips have snapped into place
properly to guarantee secure mounting.
6
Separation between two
mounting cut-outs
39.5 mm
39 mm
42 mm
46 mm
46 mm
– From a sheet metal thickness of 2 mm, the clips
should be pressed in individually.
– From a sheet metal thickness of 2.5 mm, the fan-
and-filter unit must be screwfastened in addition
(tightening torque, see section 11 "Cut-out/drilling
dimensions").
– To drill the lower holes, it is necessary to remove the
louvred grille as shown in fig. 2.
Fig. 2:
Release the louvred grille
– If transporting, it is necessary that you screw-fasten
the fan to prevent it from falling out of the mounting
cut-out.
– The fan-and-filter unit is a rotating component that
may transfer vibrations and oscillations.
Appropriate measures to decouple vibration must be
taken in advance by the company responsible for the
overall plant or system.
– The protection category can be increased by means
of the following accessories:
– IP 55 by using a pleated filter or a hose-proof hood.
– IP 56 by using a hose-proof hood.
Note:
To increase the protection category, a pleat-
ed filter or hose-proof hood must be used
for the fan-and-filter unit and outlet filter.
4.4

Notes on electrical connection

When performing the electrical connection, it is impor-
tant to observe all valid national and regional regula-
tions as well as the provisions of the responsible power
supply company. Electrical connection must only be
Rittal fan-and-filter unit assembly and operating instructions
3237.xxx
3238.xxx
3239.xxx
3240.xxx
3241.xxx
3243.xxx
3244.xxx
3245.xxx