Lithonia Lighting LEM04 Instruction Manual

Lithonia Lighting LEM04 Instruction Manual

Emergency led drivers

Advertisement

Quick Links

When using electrical equipment, basic safety precautions should always be followed, including the following:
READ AND FOLLOW ALL SAFETY INSTRUCTIONS
1.
CAUTION- To prevent electrical shock, do not mate unit connector until installation is complete and A.C.
power is supplied to the unit.
2.
CAUTION-This fixture provides more than one power supply output source. To reduce the risk of electrical
shock, disconnect both normal and emergency sources by turning off the A.C. branch circuit and by discon-
necting the unit connector.
3.
CAUTION-This is a sealed unit. Components are not replaceable. Replace the entire unit when necessary.
4.
CAUTION-Installation and servicing should be performed by qualified personnel only. De-energize before
opening.
5.
An unswitched A.C. power source of 120 to 277volts AC, 50/60Hz is required.
6.
The LEM emergency driver and A.C. driver must be on the same branch circuit.
7.
Do not mount near gas or electric heaters.
8.
The LEM emergency driver should be mounted in locations and at heights where it will not readily be subject-
ed to tampering by unauthorized personnel.
9.
The LEM emergency driver will supply 20-50VDC output at the individual rated specification for 90 minutes.
10.
This product is suitable for use in damp locations where the ambient temperature is 0ºC minimum, +50ºC
maximum. Product is also suitable for installation in sealed and gasketed fixtures. Product is not suitable for
heated air outlets and wet or hazardous locations.
11.
The use of accessory equipment not recommended by the manufacturer may cause an unsafe condition, void
warranty, and result in non-compliance with UL specifications.
12.
Do not use this equipment for other than intended use.
13.
Install in accordance with the National Electrical Code and local regulations.
14.
The emergency LED driver is for use with grounded, UL listed LED luminaire, shall be enclosed by the LED
luminaire and bonded to the grounding of LED luminaire.
15.
Lighting fixture manufacturers, electricians, and end-users need to ensure product system compatibility before
final installation.
EMERGENCY LED DRIVER FOR USE WITH
LED LUMINAIRES IDENTIFIED IN THE
MANUFACTURER'S
INSTALLATION INSTRUCTIONS
E484840
Emergency LED Drivers
Models LEM04 and LEM08
INSTRUCTION MANUAL
IMPORTANT SAFEGUARDS
SAVE THESE INSTRUCTIONS
ONE LITHONIA WAY, CONYERS, GEORGIA 30012, TELEPHONE 800-334-8694

Advertisement

loading

Summary of Contents for Lithonia Lighting LEM04

  • Page 1 Emergency LED Drivers Models LEM04 and LEM08 INSTRUCTION MANUAL IMPORTANT SAFEGUARDS When using electrical equipment, basic safety precautions should always be followed, including the following: READ AND FOLLOW ALL SAFETY INSTRUCTIONS CAUTION- To prevent electrical shock, do not mate unit connector until installation is complete and A.C.
  • Page 2 2. Mounting the LEM Emergency Driver For LEM04 A and LEM08 A: The LEM Emergency Driver should be mounted on or nearby the fixture above the ceiling. Route the flexible conduit to the fixture or junction box to make the necessary connections.
  • Page 3 4. MOUNTING THE TEST SWITCH / CHARGE INDICATOR For installation of the Test Switch / Charge Indicator, select a convenient location on the fixture so the Test Switch / Charge Indicator can be seen after installation. Allow for proper clearance inside the fixture and drill or punch a ″...
  • Page 4 LEM Series Compatibility and Suitability of Use Guidelines Addendum (Rev. A) This product is suitable for field installation with suitable LED loads including LED luminaires, DC voltage driven LED replacements for fluorescent lamps and others. There are 4 checks to determine if your luminaire is eligible for field installation.