Electrical precautions. Before servicing the pump, always shut off the main power circuit. Make sure you are wearing
insulated protective sole shoes and not standing in water. Under flooded conditions, contact your local electric company or a qualified
licensed electrician for disconnecting electrical service to the pump prior to removal.
Pumps contain oil which becomes pressurized and hot under operating conditions. Allow 2½ hours after shut down before
servicing pump.
Condition
A. Pump will not start or run.
B. Motor overheats and trips on overload.
C. Pump will not shut off.
D. Pump operates but delivers little or no water.
E. Pump starts and stops too often.
F. Large red flashing light comes on at control box.
G. Grease and solids accumulate in pit around pump.
®

Service Checklist

Common Causes
Blown panel or circuit breaker fuse, low voltage, thermal overload open, defective
capacitor circuit, impeller clogged, float switch held down or defective, incorrect wiring
in control panel, water in cap assembly.
Incorrect voltage, impeller blocked, negative head (discharge lower than intake of
pump). Defective "off" float. Pump runs continuously at low water level. Low oil level
in motor shell.
Air lock, debris under float assembly, defective switch, incoming sewage exceeds
capacity of pump.
Intake clogged with grease or sludge, pump air locked (clear vent hole), low or
incorrect voltage, clogged discharge line, operating near shut-off head.
Check valve stuck open or defective. Sump pit too small to handle incoming sewage.
Level control out of adjustment. Thermal overload tripping.
High water in pit. Check pump for clogging, or overload trip. See "A" and "D"
above.
Break up solids and run pump with water running into the pit. Allow level to lower to the
pump intake. Continue until solids are cleared from the pit.
Do not drain kitchen grease down the sink.
MAIL TO: P.O. BOX 16347 • Louisville, KY 40256-0347
SHIP TO: 3649 Cane Run Road • Louisville, KY 40211-1961
(502) 778-2731 • 1 (800) 928-PUMP • FAX (502) 774-3624
Your Peace of Mind is Our Top Priority
© Copyright 2010 Zoeller Co. All rights reserved.
12
visit our web site:
www.zoeller.com
®

Hide quick links:

Advertisement

loading