■ VR Explanation
● SOFT
This is the function to set the soft start and soft up/down times.
(Set via external VR)
- Soft start : It is a function to protect against load with large starting current
(inrush current) and it gradually increases output operates when power is
turned on while control input is applied, and is set to 50 seconds at
maximum VR. (ex : 20 mA : 50 seconds,, 12 mA : 25 seconds,)
- If VR is set to the minimum, this function does not work, and the time is
reduced as VR is changed to the left.
■ O.C
Function to protect power regulator (TPR) and load when overcurrent occurs.
(Phase control only)
- At the time of shipment, it is set to about 120 % of the product rating, and the
overcurrent detection setting value can be changed through communication.
■ Output limit function
It is a function to limit the output separately from the control input signal. It
can be set through communication and the maximum output amount is
limited according to the set value.
- Set to 100 % at the time of shipment
▍ Installation
1. Please install it perpendicularly. If the product is installed vertically in unavoidable circumstances,
please use 50% of rated current.
2. When multiple products are closely installed, please install them with keeping a distance of more than
a width of 5cm and a length of 10cm as shown in the picture.
3. In order to not block the air flow, please install the wiring duct less than the half of the heat sink height.
4. Please consider whether the air flow is good enough when installing the product. If the ambient
temperature is as low as possible in the inside then the life span of the product is increasing as the
durability and reliability of the product are improving. The operating ambient temperature is 0 ~ 40 ℃.
Please refer to the following graph. However, if the ambient temperature is higher than 40 ℃,
the maximum load current is decreasing like the below.
5. When connecting R and U, please securely fasten them with using crimp connectors since high current
flows into these terminals. If the contact surface of the connectors and terminals are poor, it may lead
to a fire since the wires and terminal gets overheated.
6. Before applying power, this model need more than the third class grounding to prevent electric shock.
This model does not have separate grounding terminal so we suggest using grounding terminal and
bracket together when install this model to a panel.
▍ Communication
1. Communication method : RS485 2-wire half-duplex
2. Communication speed : 2400, 4800, 9600, 19200 bps
3. Maximum number of connections : 31
4. Protocol : ModBus RTU, ModBus ASCII
■ Address (ID) setting
• Set the ID with DIP S/W no. 1~5
• Set 1 ~ 31 (except 0).
• When communication setting is changed,
the change is applied after reset.
ID:1
ID:3
ID:5
■ Communication setting (ModBus RTU/ASCⅡ)
Communication settings
Communication speed
2400, 4800, 9600, 19200
Protocol
ModBus RTU
ModBus ASC II
Parity bit
Even
None
Data bit
8
7
Stop bit
1
ID
1 ~ 31
Example (RTU)
Address
Division
Function Start Address
No. of Data
(ID)
Request
0x01
0x03
0x00
0x01
0x00
Address
No. of
Division
Function
Data
(ID)
Data
Response
0x01
0x03
0x02
0x00
0x00
M3.5
M3.5
M6
M6
M3.5
M6
M3.5
M3.5
M3.5
7. Tighten the screws of the terminal block with the
M6
M6
M6
specified torque.
M3.5: 0.6 ~ 1.2 N.m / M6: 4.41 ~ 4.9 N.m /
M8 : 8.82 ~ 9.80 N.m
• Circuit
• 40/55/70A
power
7.3
15.0
7.3
15.0
7.3
M3.5
15.0
M6
M3.5
M6
M3.5
M6
■ Communication protocol selection
• Set the communication protocol with DIP S/W no. 8
ID:2
■ Communication speed setting
• Set the communication speed with DIP S/W no. 6 or 7
ID:4
ID:6
2400 bps 4800 bps
Structure (RTU)
bps
Division Address(ID) Function Start Address
Request
1
1
2
bit
bit
Division Address(ID) Function
No. of Data
bit
Request
1
1
1
Structure (ASCⅡ)
Address
CRC
Division
Function
(ID)
0x01
0xD5
0xCA
Request
2
2
Address
CRC
Division
Function
(ID)
0xB8
0x44
Response
2
2
Division Address(ID) Function
Request 0x01 0x31 0x03 0x33 0x30 0x30 0x30 0x31 0x30 0x30 0x30 0x31 0x46 0x41 0x0D 0x0A
Division Address(ID) Function
Response 0x30 0x31 0x30 0x33 0x30 0x32 0x30 0x30 0x30 0x30 0x46 0x41 0x0D 0x0A
BOLD : RAM DATA
READ
READ/WRITE
Communication MAP
PROCESS
Address
0
0
1
AlarmStatus
2
CH1 Status
3
CH2 Status
4
CH3 Status
5
6
Soft Time
7
8
CH1 Output
9
CH1 Current
10
CH2 Output
LL Use Mode
11
CH2 Current
12
CH3 Output
13
CH3 Current
14
CH1 Input
15
CH2 Input
Data Length
M8
16
CH2 Input
M8
M8
17
18
CH1 Enable
19
CH2 Enable
20
CH3 Enable
21
CH1 Power Limit
22
CH2 Power Limit
23
CH3 Power Limit
24
CH1 OC Limit
M8
M8
M8
25
CH2 OC Limit
26
CH3 OC Limit
• 90/130/160 A
Address
Parameter
100
System
101
-
102
-
26.0
103
-
26.0
M8
26.0
104
M8
105
Rev
M8
106
Out Mode
110
LL Use Mode
111
Protocol
112
BPS
113
Parity
114
STOP BIT
115
DATA LENGTH
116
ADDRESS
117
R.TIME
118
CH1 Enable
119
CH2 Enable
120
CH3 Enable
121
CH1 Power Limit
122
CH2 Power Limit
123
CH3 Power Limit
124
CH1 OC Limit
125
CH2 OC Limit
126
CH3 OC Limit
Address
Parameter
200
Scan Start
201
Scan Out Mode
202
CH1 Complete
204
CH1 LL Rate
205
CH2 Complete
207
CH2 LL Rate
208
CH3 Complete
RTU
ASCⅡ
210
CH3 LL Rate
* 200: If it is 1, the status is being scanned. 0 is displayed after scanning is completed (3 channels are scanned at the same time)
* 201: Control method setting status being scanned
* 202: If it is 1, the scan is completed and the heater value is stored in the internal storage device (If it is 0, it is not saved, not scanned)
2400 bps
* 204: Set to 3 for 3 heaters (Low load malfunction concern Output 20% or less Detection prohibited)
Alarm (LED)
Alarm Description
When load power is
not applied
Power Fail
9600 bps 19200 bps
(EMG
lighting)
Fuse disconnected
When the heater is
disconnected
No. of Data
CRC
SCR Short
Internal SCR
(EMG
2
2
element shorted
flashing)
OC Fail
In case of
Data
CRC
(OC lighting)
overcurrent
2
2
Fan Fail
FAN failure
(OC flashing)
One or more
Start
No. of
LRC
LL Fail
disconnection in
Address
Data
(LL lighting)
parallel heater
4
4
2
configuration
No. of
Over Temp 60
Heat sink temperature
Data
LRC
Data
(OT flashing)
Over 60 degrees
Over Temp 80
Heat sink temperature
2
4
2
(OT lighting)
Over 80 degrees
Example (ASCⅡ)
Start Address
No. of Data
No. of
Data
LRC
Data
monitoring
Configurable
INFO
CAL
Address Parameter
100
200
1
AlarmStatus
System
Scan Start
2
CH1 Status
Scan Out Mode
3
CH2 Status
CH1 Complete
4
CH3 Status
5
-
CH1 LL Rate
6
Soft Time
Rev
CH2 Complete
7
-
Out Mode
8
CH1 Output
CH2 LL Rate
9
CH1 Current
CH3 Complete
10
CH1 Output
11
CH1 Current
12
CH1 Output
CH3 LL Rate
13
CH1 Current
Protocol
14
CH1 Input CH1 4 - 20 mA Control signal input
BPS
15
CH2 Input CH2 4 - 20 mA Control signal input
Parity
16
CH3 Input CH3 4 - 20 mA Control signal input
Stop Bit
Address
Parameter
AlarmStatus
R.Time
Address
Bit 0
Bit 1
FAN Fail
Bit 2
OC Fail
Bit 3
LL Fail
Bit 4
Over Temp 60
Bit 5
Over Temp 80
Bit 6
SCR Short
Bit 7
Power Fail
Bit 8 ~ 15
Infomation (100 ~ 199)
Explanation
SCR Product Setup Status
-
-
-
SCR Revision
Control method setting status
Whether the partial heater
break function is used
Protocol setting status
Communication speed setting status
Parity bit setting status
Stop bit setting state
Data length
ID (SCR communication number)
Response time
Decide whether to use CH1
Decide whether to use CH2
Decide whether to use CH3
CH1 output limit setting
CH2 output limit setting
CH3 output limit setting
Set CH1 overcurrent value
Set CH2 overcurrent value
Set CH3 overcurrent value
Calibration (200 ~ 299)
Explanation
Partial load disconnection scan
Control mode for partial
load disconnection scan
CH1 heater value saved
CH1 Parallel heater breaks
CH2 heater value saved
CH2 Parallel heater breaks
CH3 heater value saved
CH3 Parallel heater breaks
Explanation about SCR Alarm
Checking list
1. Confirmation of load power voltage for each channel
(Example: Check 1CH load voltage when 1CH POWER Fail)
2. Check that the load power breaker is ON (Reset, turn on / off)
3. SCR load power input terminal R, S, T wiring check
1. Open the upper case of SCR and check the fuse disconnection
(Shot is normal when measuring the fuse tester after the load power is turned off)
1. Check the resistance value of the load connected to the SCR (disconnection and disconnection)
2. Check the SCR heater connection terminals U, V, W wiring
1. Symptom: When 4 mA and control input are not applied, load current When more than 5 A flows.
2. Confirm: Check several channel SCR Short
3. Generation channel 4 - 20 mA Input part voltage is less than 0.4 V, Ensure current is measured in
clampmeter (SCR failure if confirmed, replacement required)
1. When the current exceeding the OC Limit setting value flows to the load
2. Clamp meter connected to overcurrent identified channels U, V, W Check the current on the wiring.
1. Make sure that the cooling fan on the bottom of the SCR is rotating
2. Make sure that there is foreign substance in the cooling fan
1. Check if the heater value is saved using the Scan function (communication)
2. If you do not know whether or not you have scanned the control signal (4 - 20 mA)
When there is no scan, DIP SW 2 turns OFF and scan progress, LL LED
When it changes to flashing, it changes to switch ON position again.
3. Check the resistance value of the heater. Comparison of the resistance value of the part
(When the resistance value becomes high)
1. Check if cooling fan is rotating well
2. Identify the cooling unit inside the panel
3. If an alarm occurs immediately upon power-on, the SCR internal fault.
MODBUS
MODBUS
Protocol
RTU
ASCII
LRC
END
2400, 4800, 9600,
Speed
19200 bps
END
Parity
Even
None
Data bit
8
7
Stop bit
1
1
ID
1 ~ 31
Explanation by address
Process (0 ~ 99)
Explanation
Setting range
Unit
Alarm status information
Refer to Bit Information
CH1 Status information
Refer to Bit Information
CH2 Status information
Refer to Bit Information
CH3 Status information
Refer to Bit Information
-
-
-
Soft start Setting time
0 ~ 60
sec
-
-
-
SCR CH1 Yield
0 ~ 100
%
SCR CH1 Load current value
0 ~ CT (max)
(x10) A
SCR CH2 Yield
0 ~ 100
%
SCR CH2 Load current value
0 ~ CT (max)
(x10) A
SCR CH2 Yield
0 ~ 100
%
SCR CH2 Load current value
0 ~ CT (max)
(x10) A
0 ~ 100
%
0 ~ 100
%
0 ~ 100
%
BIT Information
CH1 Status
CH2 Status
CH3 Status
1
2
3
4
-
Power Fail
Power Fail
Power Fail
LL Fail
LL Fail
LL Fail
OC Fail
OC Fail
OC Fail
SCR Short
SCR Short
SCR Short
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
Setting range
Unit
0x0130 : TPR3SLEP
0 : phase control 1 : fixed cycle cycle control
2 : Variable cycle cycle control
0 : Disable partial heater disconnection function
1 : Using partial heater disconnection function
2 : ASCII, 3 : RTU
0 : 2400, 1 : 4800, 2 : 9600, 3 : 19200
0 : None, 1 : Odd, 2 : Even
1, 2
7, 8
1 ~ 31
0 ~ 10
0 : Do not use this channel
1 : Use this channel
0 ~ 100
%
0 ~ 100
%
0 ~ 100
%
0 ~ CT (max)
(x10) A
0 ~ CT (max)
(x10) A
0 ~ CT (max)
(x10) A
Setting range
Unit
0 : Operating, 1:LL Scan
0 : phase control 1 : fixed cycle cycle control
2 : Variable cycle cycle control
control, 2 : Variable cycle cycle control
1 ~ 6
EA
0 : No scan data, 1 : Complete
1 ~ 6
EA
0 : No scan data, 1 : Complete
1 ~ 6
EA
Need help?
Do you have a question about the TPR-3SL-EP and is the answer not in the manual?