PROFINET/Ethernet
5.1 PROFINET IO
Slot 4 (Powerline status) IW x:
Input word PLB Errors: IW x (unsigned 16):
Bit 0: Short circuit PL – Phase
Bit 1: Short-circuit PL-B – FE
Bit 2: Short-circuit PL-A – FE
Bit 3: Overvoltage
Bit 4: Core Dump
Bit 5: Error at left modem
Bit 6: Right modem inserted
Bit 7: Log backup
Bit 8: Rescue mode
Bit 9 to 15: System reserve
Byte x
7
LogBack
Byte x+1
7
Input word PLB Warnings: IW x+2 (unsigned 16):
Bit 0: Undervoltage
Bit 1 to 15: System reserve
Byte x+2
7
Byte x+3
7
Input byte signal quality: IW x+4 (unsigned 8):
Status of the powerline connection.
0 = No connection;
100 = connection.
Byte x+4
7