Appendix B
A 20 Second Time-Delay between Compressor Starts is Built Into the Module
4
Reset Contacts
(Optional)
Rack Controller
HPS/LPS
6
VSR
7
Suctio
Suction
R (+5)
Pressure
W (sig)
n
B (gnd)
Discharge
R (+5)
Pressure
W (sig)
B (gnd)
Oil
R (+5)
Pressure
W (sig)
B (gnd)
1
Motor
Temp
1
Discharge
Temp
Unused
LonWorks
Communication
Notes:
1.
Connections for Motor Temp, Discharge Temp, and echelon communications are all polarity insensitive.
2.
L1 must be jumpered to 240V or 120V depending on line voltage. The drawing shows wiring for 120V. The L1
input is used to power the alarm output.
3.
The compressor is loaded when the solenoid is energized and unloaded when de-energized.
4.
A normally closed set of contacts can be added to reset power to the module. Useful for remotely resetting a
module out on an Alarm Failure
5.
The diagnostic alarm code is flashed by the yellow alarm light during a compressor alarm.
6.
The system safeties are monitored on the Slimits Input. This input actually powers the contactor output and is
switched through the module. See section 1.2 for details on the additional required system safeties.
7.
A voltage sensing relay (VSR) (or an equivalent method) should be used to detect if power is lost to the line side of
the contactor (i.e. circuit breaker has tripped).
Carlyle Compressor Div.
Carlyle LonCEM
Slimits
Ccall
P O Box 4808
Phone: 800-462-2759
Wiring Schematic
2
240V 120V
L1
Com
CR1
CR2
Liq M
Liq D
UN
Oil
VI
AL
Fax: 315-432-3274
13
XL Contactor Coil
PW Contactor Coil
Motor Cooling Coil
Unloader Coil
Oil Solenoid
Econ
Solenoid
Vi Coil
Alarm
Output
Syracuse, NY 13221