Circuit Breakers (Iec); Abb Miniature And Molded Case Circuit Breakers - ABB ACS880-01 Hardware Manual

Hide thumbs Also See for ACS880-01:
Table of Contents

Advertisement

Note:
1. See also section
2. The UL listed fuses in this hardware manual are the required branch circuit protection
per NEC.
3. Fuses are required as part of the installation. Fuses are not included in the base
drive configuration and must be provided by others.
4. Recommended drive fuses must be used to maintain drive UL listing. Additional
protection can be used. Refer to local codes and regulations.
5. When installing a drive, always follow installation instructions and NEC requirements.
6. In multicable installations, install only one fuse per phase (not one fuse per
conductor).
7. Fuses with a higher current rating than the specified must not be used.
8. Fuses with a lower current rating than specified can be used if they are of the same
voltage and are UL 248 listed fast acting or high speed fuses.
9. A fuse of a different class can be used at the high fault rating where the I
2
I
t of the new fuse are not greater than those of the specified fuse.
10. UL 248 listed, fast acting or high-speed fuses from other manufacturers can be
used, if they meet the rating requirements specified in the rules above.
11. Alternative fuses can be used if they meet certain characteristics. For acceptable
fuses, see the manual supplement

Circuit breakers (IEC)

ABB miniature and molded case circuit breakers

The table below lists the circuit breakers that can be used with the drive.
ACS880-
Frame
01-...
U n = 230 V
04A6-2
R1
06A6-2
R1
07A5-2
R1
10A6-2
R1
16A8-2
R2
24A3-2
R2
031A-2
R3
046A-2
R4
061A-2
R4
1) Maximum allowed rated conditional short-circuit current (IEC 61800-5-1) of the electrical power
network
Implementing short-circuit and thermal overload protection (page 78)
ABB miniature circuit
breaker
Type
S 203 M/P-B/C 10
S 203 M/P-B/C 10
S 203 M/P-B/C 16
S 203 M/P-B/C 16
S 203 M/P-B/C 20
S 203 M/P-B/C 32
S 203 M/P-B/C 50
S 803 S-B/C 75
S 803 S-B/C 80
(3AXD50000645015
ABB moulded case circuit breaker (Tmax)
kA
1)
5
5
5
5
5
5
5
10
10
Technical data 213
Peak
[English]).
Type
-
-
-
-
-
-
-
-
-
and
kA
1)
-
-
-
-
-
-
-
-
-

Advertisement

Table of Contents
loading