Accessing the TRIM Menu
Feedback Output Test
The feedback signal is automatically obtained in the positioner calibration process. It is
possible to measure this signal to check possible differences between the control and
feedback signals before putting the positioner into operation.
To test the signal, connect a 4 to 20 mA current generator to terminals 1 (+) and 3
(-). Connect a 24 Vdc voltage source in series with a multimeter on the current scale at
terminals 4 (+) and 5 ( - ).
Figure 8-35 Feedback Test Link
Set the current generator to 4 mA and gradually increase by checking the output signal
(feedback) on the multimeter. See the graph below for 4 to 20 mA current values.
The output signal must be the same as the current generator, if there is a difference,
perform the TRIM adjustment procedure indicated in the previous item.
76
Press ENTER ○ for 3 seconds to enter the menu.
Use the DOWN key to go to the TRIM option. The UP key returns to the
previous option.
Use the ENTER key ○ to select the option.
Set the control signal to 4 mA, then confirm the 4 mA point with the ENTER ○
key.
Adjust the control signal to 20 mA and also confirm the 20 mA point with the
ENTER ○ key.
If you wish to exit the menu without making changes, DO NOT use ENTER ○, use
the UP key for 3 seconds and return to the main menu.