Mitsubishi Electric M70V Series Connection Manual page 84

Table of Contents

Advertisement

(2) LED
LED
Function
24IN
24VDC input check
5OUT
Internal output voltage check
Communication error of the station
ALM1
designated by rotary switch "SCAN1"
Communication error of the station
ALM2
designated by rotary switch "SCAN2"
Communication error of the station
ALM3
designated by rotary switch "DIO"
(3) Rotary switch
Set the address (station No.) assignment in DI/DO: 32/32 point units. Set using SCAN1, SCAN 2 and DIO rotary
switches. The assignment address is changed with the rotary switch setting.
CF35
Scan
DI:32
[Address]
X00
X1F
Scan
DI:32
[Address]
X20
X3F
CF31
Digital
DI:32
[Address]
X40
X5F
Rotary switch
SCAN1
SCAN2
DIO
(Note)
Set each different station Nos. for SCAN1, SCAN2 and DIO. Up to 8 stations can be used in a part
system. Set the Nos. from 0 to 7.
Status
Color
Normal
Green
Lit
Green
Lit
Red
Not lit
Red
Not lit
Red
Not lit
Scan
DO:32
[Address]
Y00
Y1F
Scan
DO:32
[Address]
Y20
Y3F
CF33
Digital
DO:32
[Address]
Y40
Y5F
For scan input/output station No. setting 32points/32points (Normally set to "0")
For scan input/output station No. setting 32points/32points (Normally set to "1")
For digital input/output station No. setting 32points/32points (Normally set to "2")
M70V Series Connection Manual
Remedy
At fault
Not lit
24VDC voltage check
Not lit
Contact the MITSUBISHI service dept.
Check the station No. designation by the rotary
Lit
switch of the remote I/O unit.
Check the station No. designation by the rotary
Lit
switch of the remote I/O unit.
Check the station No. designation by the rotary
Lit
switch of the remote I/O unit.
0
SCAN1
Standard setting
0
SCAN2
0
DIO
Description
2.7 Scan I/O Unit
SCAN1
0
SCAN2
1
DIO
2
59