MITSUBISHI CNC
4 Connection
Wiring the cables to the CC-Link terminal block
(1) Remove the sheath of the cable and isolate each internal wire from the shield mesh.
(2) Remove the shield mesh and the coat of each internal wire. Twist the core wires.
Shielded twisted cable (with 3 wires)
(3) In the intermediate station, twist together the same wires or the shield meshes of the cables from/to the
previous/next station.
(4) In the final station, process the provided terminator as follows to attach to the station.
Cut
(5) Insert the core wire into the opening of the terminal block. Hold the wire tight with a flat-blade screwdriver.
Check the screws on the terminal are loose enough before inserting the wires into the openings.
In the intermediate station
Flat-blade driver
(6) After wiring cables to the terminal block, Mount the terminal block into the CC-Link connector and fix it with a
flat-blade screwdriver.
114
Shield mesh
Terminator
Cut
In the final station
To the
To the
previous
next
station
station
7mm
Approx.
Shorten the
coated part
Bend the lead wires
(Note 1)
Do not solder-plate the core wire,
which leads a defective cable contact.
(Note 2)
Make sure the lead wires are kept inserted
when mounting the terminator.
Terminator
DA wire DB wire