5.1.4 ADVANCED SETUP
N.B.! The appearance and content of this menu var-
ies depending on the type of air handling unit and
functions and/or options selected. A code and a
special training are needed to access this menu.
Attention: The settings range for most of the
functions is defined for maximal flexibility. The
factory setting is the advised setting, deviating
from this setting requires carefull considera-
tion.
Stop fan with 0...10V
Function only availalbe if "demand control" function has been selected
in basic setup. With this function, the fans can be stopped if the 0...10V
control signal is below or above a specified setpoint. The control signal is
connected to the analogue input K2.
Setting
Settings
Factory
range
setting
Stop if <Vlow
No
Yes
Yes
Vlow
0...10V
0,8V
Stop if >Vhigh
No
Yes
Yes
Vhigh
0...10V
10,0V
Second 0...10V control signal
Function only availalbe if "demand control" function has been selected
in basic setup. With this function, a separate 0...10V control signal for
the extract air can be activated. The control signal is connected to the
analogue input K3.
Setting
Settings
Factory
range
setting
0...10V on K3?
No
No
Yes
Control
Exhaust
Exhaust
Supply
22
ADVANCED SETUP
ADVANCED SETUP
STOP FAN WITH 0...10V
2ND 0...10 CONTROL SIGNAL
CONSTANT PRESSURE
SOFT STOP
START TORQUE
ADVANCED SETUP
STOP FAN WITH 0...10V
2ND 0...10 CONTROL SIGNAL
CONSTANT PRESSURE
SOFT STOP
START TORQUE
Operation and maintenance
instructions – CLASS UNIT TAC5
Stop fan when pressure alarm
Possibility to stop the fans automatically in case of a pressure
alarm.
Setting
Settings
Factory
range
setting
Stop fans
No
No
Yes
Start torque
Possibility to change the fans's starting torque.
Setting
Settings
Factory
range
setting
Start Torque
0...100%
2%
Deactivate softstop
With this function, the "OFF" function is deactivated.
Setting
Settings
Factory
range
setting
Softstop
Yes
No
No
Temperature
In this menu advanced temperature control parameters can
be modified.
Supply air involves keeping a constant supply air temperature
without consideration to the load in the premises.
Extract air involves keeping a constant temperature in the
extract air duct (premises), by modulating the supply air
temperature.
The reaction speed of capacity control signal can be modified.
A higher Setting will result in a smoother control; a lower Set-
ting will result in a faster reaction speed. but also greater risc
of oscillations.
Setting
Settings
Factory
range
setting
Supply or Extract tempe-
Supply
Supply
rature control?
Extract
Reaction speed
1...10
1
Supply air, min
0...20°C
15,0°C
Supply air, max
16...50°C
28,0°C
Stop fan if T°Supply <5°C
No
No
Yes
Operation and maintenance
instructions – CLASS UNIT TAC5
ADVANCED SETUP
2ND 0...10 CONTROL SIGNAL
CONSTANT PRESSURE
STOP FAN
START TORQUE
DEACTIVATE SOFTSTOP
ADVANCED SETUP
CONSTANT PRESSURE
STOP FAN
START TORQUE
DEACTIVATE SOFTSTOP
TEMPERTURE
ADVANCED SETUP
CONSTANT PRESSURE
DEACTIVATE SOFTSTOP
TEMPERATURE
BOOST
POST VENTILATION