7.6 TYPE 6: FIRE ALARM
- Conditions:
• Fire alarm input must be connected to a fire detection system
- Causes:
• Activation of fire alarm input, IN3, connected to a fire detection system.
IN3 can be configured to work as NO open contact by default or as NC if configured so in the advanced setup.
- Effects:
Displayed on HMI TACtouch
Text displayed
F.10
FIRE ALARM
F.11
End of the fire alarm
AL1 relay
O.R.1
Alarm status
/
* The fans are stopped by default in the event of a fire alarm but, via the advanced setup, it is
possible to configure a fixed airflow for supply (contact IN7 needs to be closed) and for exhaust
(contact IN8 needs to be closed).
32
LED ALARM
RED
TAC control board
LED ALARM
LED AF
ON
/
Auto reset: no
Operation and maintenance
instructions – CLASS UNIT TAC5
7.7 TYPE 7: MAINTENANCE ALARM
- Conditions:
• the running hours feature must be enabled in advanced setup
- Causes:
• SERVICE ALARM: the fan operating time (in hours) has exceeded the configurable threshold
• STOP FAN: the fan operating time (in hours) has exceeded the configurable threshold. This alarm stops the fans
- Effects:
LED Pa
M.10
Maintenance 3 months
/
M.11
Maintenance 6 months
M.21
Operating hours
M.22
Operating hours - AHU off
Fans
AL1 relay
*
Alarm status
* unless the status has been changed in advanced setup
7.8 TYPE 8: ALARM INDICATING A COMMUNICATION BREAKDOWN
BETWEEN THE TAC CIRCUIT AND THE HMI
- Conditions:
• User interface is connected
- Causes:
• Communications failure between the TAC circuit and the HMI
- Effects:
CB COM ERROR
AL1 relay
Alarm status
Operation and maintenance
Displayed on HMI TACtouch
Text displayed
TAC control boards
O.R.1
LED ALARM
/
ON
Reset via "fan run time" (TACtouch) or "alarm menu" (App)
Displayed on HMI TACtouch
Text displayed
LED ALARM
TAC control board
O.R.1
LED ALARM
/
/
Auto reset: yes
instructions – CLASS UNIT TAC5
LED ALARM
LED Pa
RED
/
LED AF
Fans
Stopped if SERVICE STOP
/
*
FAN
LED Pa
Red
/
LED AF
Fans
/
/