4 Operation
- Measuring Type: multi-point/timed avg.
- Volume Flow Unit: m
- Correction Factor: 1% to 200%
In a multi-point measurement, a mean value is calculated from the
individual measuring values.
In a timed average measurement, a mean value is calculated over a
certain period.
Several points can be measured. This generates a timed
average/multi-point total mean value.
2
Use
to select the required parameter and make settings.
3
Press
or
to exit the menu.
Carrying out the measurement
A suitable probe is connected to the testo 440.
1
Remove the protective cap from the probe head.
For measurements in flows with a known direction, the arrow mark on
the probe head must point in the direction of flow.
2
Move the probe into the flow.
3
Align the probe with the assumed flow axis.
4
Read off the readings.
Low flow velocities may result in greater measurement uncertainty
during temperature and humidity measurement.
5
Carry out the measurement and save the measuring values.

4.5.6 Funnel volume flow application

Volume Flow]
A volume flow rate funnel is required to determine the flow rate on ventilation
systems. The measurement can be carried out with a compatible vane probe in
34
GlobalTestSupply
www.
3
/h, cfm, l/s, m
3
/s
[Funnel
.com