ESPRIT-Addressable Repeater User Manual
CONFIGURING THE SYSTEM
When the system is installed and is ready to be commissioned, configure as follows:
•
Set the network options using the CONFIG option.
•
Set the panel user interface controls (Time & Date, Display contrast, internal buzzer
volume, etc.), using the MAIN MENU described below.
•
Any alarm or fault events, system status etc., can be viewed using the REPORT
menus, described below.
Accessing the Menu Structure
Power-on the panel. Any faults detected will be displayed, accompanied by a warning tone.
Press the Mute Buzzer button to silence the warning tone. Resolve any faults before
proceeding.
Next proceed by pressing the ✓ button, the LCD unit displays the following Access Level 2
Menu (see picture below):
To access the menu structure:
•
Turn Activate Controls key switch clockwise to On
or
•
use the keypad to enter Authorised User (Access level 2) code 1111:
•
Press ✓ key to select Access level 2. The digital display will show the following
message:
Enter Level 2 Access Code
o Use Up/Down arrow keys to increase/decrease the number value
o Use Left/Right arrow keys to move to the next digit in the 4-digit sequence
o When all 4 digits have been set to the code 1111, press the ✓ key again
o The LCD unit displays the Access Level 2 Main Menu (see picture below),
which is available for operation
Note: Access level 2 Menu will deactivate after 30 sec if not used.
On the LCD screen, the box surrounding the menu icon is the cursor; this can be navigated
through the menu options by using the Left/Right arrow keys to select required menu option
and then pressing the ✓ key.
The Left/Right and Up/Down arrow keys can then be used to access further sub-menus and
options within the main menus.
Press ✓ key to select required sub-menu or option and to make changes to a selected
option.
Where there are options that have adjustable values, these are altered with the Up/Down
arrow keys followed by pressing ✓ key, when required value is reached.
Use the return
key to exit all menus and options.
Approved Document Ref: UI-ESA-03 Issue 2.0
CONFIGURING THE SYSTEM
21