NTRODUCTION
This manual covers
programming and
the ESPRiT Argus Fire Alarm Control Panels for One to Two Loop and One to Four Loop
Haes Systems Ltd, Unit 3, Horton Industrial Park, West Drayton, Uxbridge, UB7 8JD
Model Number
Control and indicating equipment for fire detection and fire alarm systems for buildings.
Output to fire alarm devices, dependency type 'A', test condition
Power supply equipment for fire detection and fire alarm systems for buildings.
ESPRIT-ADDRESSABLE
Haes Systems Ltd declare that the products identified below conform to the essential requirements
specified in the Construction Products Regulation CPR305/2011/EU.
REPEATER INSTALLATION,
In addition, the product complies with the following:
Low Voltage Directive 2014/35/EC, EN60950-1: 2006 Safety of information technology equipment
COMMISSIONING &
Electromagnetic Compatibility Directive 2014/30/EC EN61000-6-3:2007 + A1:2011 Emissions,
Class B EN50130-4: 2011 +A1:2014 Immunity, Product Family Standard.
OPERATING MANUAL
This product has been designed to comply with the requirement of the low voltage safety and the
EMC directives. Failure to follow the instructions may compromise its adherence to this standard.
This manual covers the installation, programming and commissioning of
European Standard EN54-2 : 1997 + A1 : 2006
Provided Options (with requirements):
European Standard EN54-4 : 1998
the Esprit-Addressable Repeater
18
the installation,
commissioning of
Addressable

Advertisement

Table of Contents
loading

Summary of Contents for Haes ESA-2001

  • Page 1 European Standard EN54-4 : 1998 Power supply equipment for fire detection and fire alarm systems for buildings. ESPRIT-ADDRESSABLE Haes Systems Ltd declare that the products identified below conform to the essential requirements specified in the Construction Products Regulation CPR305/2011/EU. REPEATER INSTALLATION,...
  • Page 2: Introduction

    ESPRIT-Addressable Repeater User Manual INTRODUCTION INTRODUCTION Haes Technologies Ltd, Unit 3, Horton Industrial Park, West Drayton, Uxbridge, UB7 8JD Model Number ESA-2001 Haes Technologies Ltd declare that the products identified above conform to the essential requirements specified in the Construction Products Regulation CPR305/2011/EU.
  • Page 3: Safety

    ESPRIT-Addressable Repeater User Manual SAFETY SAFETY IMPORTANT NOTICE PLEASE READ THIS MANUAL CAREFULLY BEFORE HANDLING THE EQUIPMENT AND OBSERVE ALL ADVICE GIVEN WITHIN IT. THIS PARTICULARLY APPLIES TO THE PRECAUTIONS NECESSARY TO AVOID ELECTRO-STATIC DISCHARGE Important Safety Notes The panel is safe to operate provided it has been installed in compliance with the manufacturer’s instructions and used in accordance with this manual.
  • Page 4: Cautions

    ESPRIT-Addressable Repeater User Manual SAFETY Cautions Equipment Guarantee This product has been manufactured in conformance with the requirements of all applicable EU Council Directives and is not guaranteed unless the complete system is installed and commissioned in accordance with the laid down national standards by an approved and competent person or organisation.
  • Page 5: Table Of Contents

    ESPRIT-Addressable Repeater User Manual TABLE OF CONTENTS TABLE OF CONTENTS INTRODUCTION ........................2 SAFETY ..........................3 IMPORTANT NOTICE ........................... 3 Important Safety Notes ........................3 Disclaimer............................3 Warnings ............................3 Cautions ............................4 TABLE OF CONTENTS ......................5 General Description of the Equipment ....................7 Repeater Cabinet ..........................
  • Page 6 ESPRIT-Addressable Repeater User Manual TABLE OF CONTENTS General User Controls ........................16 Available Functions ........................16 Authorized User Controls ......................16 Available Functions ........................17 Authorised User Menu Options ....................17 Engineer Controls .......................... 17 Available Functions ........................18 Engineer Menu Options ......................18 Panel Alarm Conditions ........................
  • Page 7: General Description Of The Equipment

    Quality, reliability, ease of use and feature rich are attributes that are consistent across the entire range of Haes fire alarm control panels. The ESPRiT Addressable panels encompass all these attributes, to provide the fire alarm engineer’s panel of choice.
  • Page 8: Repeater Cabinet

    ESPRIT-Addressable Repeater User Manual TABLE OF CONTENTS Repeater Cabinet Circuit Description/Function TPC2879-206 PSU PCB PSU (+ -) 28.0VDC input from an EN54-4 compliant power supply 28V / 0V (+ -) 28V output, fused at 500mA TPCA05 Network Card PCB COMS A (+ -) / COMS B (+ -) RS485 serial communication terminals connected to form a Fault Tolerant or Legacy network.
  • Page 9: Technical Specification

    ESPRIT-Addressable Repeater User Manual TABLE OF CONTENTS Technical Specification General Specification Enclosure Steel IP30. Epoxy powder coated Interpon Radon, silver grey. Cabling Fire resistant screened cable, minimum size 1 mm . Max cable length 1 Km (20 Ohm). FireBurn, FP200 or equivalent (max capacitance 1uF, max inductance 1 millihenry).
  • Page 10: Installation

    Further copies of this User Instruction Manual are available from the website www.https://haes-tech.com. This equipment is designed to be operated from 230V AC 50/60 Hz mains supplies and is of Class I construction.
  • Page 11: Installing The System

    ESPRIT-Addressable Repeater User Manual INSTALLATION Installing the system General Care should be taken with regards to avoiding the close proximity of high voltage cables or areas likely to induce electrical interference. Earth links should be maintained on all system cables and grounded in the control panel. The detection and sounder circuit cabling is classed as extra low voltage and must be segregated away from mains voltage.
  • Page 12: Power Connections

    ESPRIT-Addressable Repeater User Manual INSTALLATION Power connections Note: All connections must be carried out in accordance with local requirements and regulations. Do not connect the power supply to the panel until you are fully conversant with the layout and features of the equipment. The incoming power supply should be brought into the panel via one of the knockouts provided.
  • Page 13: Operating Instructions

    ESPRIT-Addressable Repeater User Manual OPERATING INSTRUCTIONS OPERATING INSTRUCTIONS Repeater Control and Indications Front Panel The front panel contains: • LCD Display screen • 5 button control keypad • Up/down/left/right arrow keys and enter (✓) key curser control keypad • Panel status LED indicators •...
  • Page 14: Keypads

    ESPRIT-Addressable Repeater User Manual OPERATING INSTRUCTIONS Keypads Use to resound the alarms after they have been silenced. Can also be used to invoke full evacuation. Resound Alarms Use to silence the sounders during an alarm condition. Silence Alarms Resets the panel back to standby mode. Reset System Mutes the panels internal fire and fault buzzer.
  • Page 15: Status Led Indicators

    ESPRIT-Addressable Repeater User Manual OPERATING INSTRUCTIONS Status LED Indicators LED Name LED ON LED Pulsing Indicates mains and/or battery Supply Healthy: supply is present. General Fire: Indicates panel is in alarm condition Indicates panel is in the unsilenced that has been silenced. alarm condition General Fault: Indicates one or more faults are...
  • Page 16: Software Downloads

    OPERATING INSTRUCTIONS Software Downloads The Haes Configuration panel software enhances the ease of programming of the panel, by enabling the engineer to both download existing panel configurations for amendment, or programme new panel configuration ‘off panel’ before uploading onto the panel. Programming of the configuration uses easy to follow tables.
  • Page 17: Available Functions

    ESPRIT-Addressable Repeater User Manual OPERATING INSTRUCTIONS o When all 4 digits have been set to the code 1111, press enter ✓ key once again o The MAIN MENU will become available for operation. Once the code is entered, or the Activate Controls key is turned to On, the LCD unit will display the MAIN MENU.
  • Page 18: Available Functions

    ESPRIT-Addressable Repeater User Manual OPERATING INSTRUCTIONS Use the Scroll Control keypad up/down and left/right arrows, and the enter ✓ key to navigate the Access level 3 menu. Note: The Access level 3 code 3333 is the factory default. Available Functions The functions that can be performed at Access level 3 are: •...
  • Page 19: Panel Alarm Conditions

    ESPRIT-Addressable Repeater User Manual OPERATING INSTRUCTIONS Panel Alarm Conditions Fire Alarm Condition The display shows location/origin of the fire alarm and the total number of zones in a fire alarm condition. If two or more zones enter the fire alarm condition, the display also shows the location of the last zone to enter a fire alarm condition.
  • Page 20: Functionality During A Loop Fault

    ESPRIT-Addressable Repeater User Manual OPERATING INSTRUCTIONS o The extension LED Board is halted o Fault relay is active o Fire alarms can still be detected and controlled by the panel. • Power Supply Board o System Fault LED pulsing o General Fault LED pulsing o Power Supply Fault LED pulsing o Fault relay activated o Mains or battery power will still operate the panel.
  • Page 21: Configuring The System

    ESPRIT-Addressable Repeater User Manual CONFIGURING THE SYSTEM CONFIGURING THE SYSTEM When the system is installed and is ready to be commissioned, configure as follows: • Set the network options using the CONFIG option. • Set the panel user interface controls (Time & Date, Display contrast, internal buzzer volume, etc.), using the MAIN MENU described below.
  • Page 22: Main Menu

    ESPRIT-Addressable Repeater User Manual CONFIGURING THE SYSTEM MAIN MENU The options are: • MAIN MENU o CONFIG ▪ OPTIONS ▪ PASSWORD ▪ DEFAULT o REPORT ▪ ALARM ▪ FAULT ▪ DISABLE ▪ TEST ▪ OTHER o TIME & DATE ▪ Time &...
  • Page 23: Main Menu: Config

    ESPRIT-Addressable Repeater User Manual CONFIGURING THE SYSTEM MAIN MENU: CONFIG To access the CONFIG menu: • On the MAIN MENU, use Left/Right arrow keys to move cursor box to CONFIG icon • Press ✓ key to select the CONFIG icon. The digital display will show the following message: Enter Level 3 Access Code •...
  • Page 24: Config Menu: Default

    ESPRIT-Addressable Repeater User Manual CONFIGURING THE SYSTEM CONFIG MENU: DEFAULT To return the panel to its factory default settings, access the DEFAULT menu: • Highlight the DEFAULT option under the CONFIG menu and press ✓ key. • The following information will be displayed on the digital display: ARE YOU SURE? SET PANEL DEFAULTS •...
  • Page 25: Report Menu: Fault

    ESPRIT-Addressable Repeater User Manual CONFIGURING THE SYSTEM REPORT MENU: FAULT To get FAULT events information: • Under REPORT sub-menu, select FAULT option and press ✓ key to select it. • Fault info will be displayed in the following manner: FAULT A nn F nn D nn T nn O nn...
  • Page 26: Report Menu: Test

    ESPRIT-Addressable Repeater User Manual CONFIGURING THE SYSTEM REPORT MENU: TEST To get TEST events information on system test modes enabled: • Under REPORT sub-menu, select TEST option and press ✓ key to select it. • TEST info will be displayed in the following manner: TEST A nn F nn D nn T nn...
  • Page 27: Main Menu: Time&Date

    ESPRIT-Addressable Repeater User Manual CONFIGURING THE SYSTEM MAIN MENU: TIME&DATE The TIME&DATE sub-menu is used to set the system clock and to set the period where the system clock is moved forward 1 hour, to reflect local Daylight Savings Time (DST): •...
  • Page 28: Main Menu: Lamp Test

    ESPRIT-Addressable Repeater User Manual CONFIGURING THE SYSTEM ▪ Monday – Sunday Ends: LAST/1 Jan - DEC - adjust the date, to show when the local Day Light Savings time ends (e.g. – Ends: 4th Tuesday OCT) ▪ Auto Update DayLight Savings: YES/NO - adjust to turn on or off the automatic switching of the system clock forward by 1 hour to match local DST ▪...
  • Page 29: Main Menu: Buzzer

    ESPRIT-Addressable Repeater User Manual CONFIGURING THE SYSTEM MAIN MENU: BUZZER To set the volume for the panel internal buzzer, open the BUZZER menu: • Under MAIN MENU, highlight the BUZZER option and then press ✓ key to select it. • Under BUZZER Menu the following option will be available: VOLUME •...
  • Page 30: Menu Breakdown

    ESPRIT-Addressable Repeater User Manual CONFIGURING THE SYSTEM MENU Breakdown Approved Document Ref: UI-ESA-03 Issue 2.0...
  • Page 31: Service And Maintenance

    ESPRIT-Addressable Repeater User Manual SERVICE AND MAINTENANCE SERVICE AND MAINTENANCE The product must be maintained for operation, including periodic checks, in accordance with applicable codes of practice, national standard regulations and local instructions for fire systems appropriate to the country and location of the installation. It is the responsibility of the system user to ensure it is regularly serviced and maintained in good working order.
  • Page 32: Schedule Of Testing

    ESPRIT-Addressable Repeater User Manual SCHEDULE OF TESTING SCHEDULE OF TESTING This section to be used to record ALL weekly tests of the fire alarm system. Date & Device Tested & Initials of Comments (if any) Location Tester Time of Test Approved Document Ref: UI-ESA-03 Issue 2.0...
  • Page 33 ESPRIT-Addressable Repeater User Manual SCHEDULE OF TESTING Date & Device Tested & Initials of Comments (if any) Location Tester Time of Test Approved Document Ref: UI-ESA-03 Issue 2.0...
  • Page 34 www.haes-tech.com...