ESPRIT-Addressable Repeater User Manual

Panel Alarm Conditions

Fire Alarm Condition

The display shows location/origin of the fire alarm and the total number of zones in a fire
alarm condition.
If two or more zones enter the fire alarm condition, the display also shows the location of the
last zone to enter a fire alarm condition.
In addition:
The General Fire LED and the respective Detection Zone LED(s) will be illuminated.
The fire alarm bells/sounders will activate (depending on how they are programmed
to respond).
To silence the internal buzzer, press the Mute Buzzer button.
To silence the bells, press the Silence Alarm button.
To reset the panel, press the Reset System button.

Fault Condition

If the panel detects a fault condition, the display will indicate the number and nature of the
fault(s). The internal buzzer will sound with an intermittent tone and the amber General
Fault LED will illuminate pulsing, and any other specific Fault LED indications will be
illuminated.
Press the Left/Right and Up/Down arrow keys to scroll through the list of faults.
Press the Mute Buzzer
LED will change to steady illumination
Note: The fault condition is non-latching (except System Fault) and the indications will
automatically be cleared when the fault is remedied. Press the Reset System
clear a Fault.
Note: If silenced, the buzzer will re-sound when a new fault occurs.

Functionality During a System Fault

A system fault is indicated when a processor, controlling a function in the panel, has a
watchdog time-out or processor failure. In the event of a system fault, the affected board
may not be functional. The following indications may be observed:
Display Board (Main control board)
o System Fault LED only illuminated
o Continuous buzzer sound
o Display board (main control board) is halted and no other indication or control
is possible
o Fault relay is activated
Extension LED board (optional)
o System Fault LED continuous and General Fault LED pulsing
Approved Document Ref: UI-ESA-03 Issue 2.0
key to silence the internal buzzer. The General Fault amber
OPERATING INSTRUCTIONS
key to
19