INSTALLATION

Power connections

Note: All connections must be carried out in accordance with local requirements and
regulations.
Do not connect the power supply to the panel until you are fully conversant with the layout
and features of the equipment.
The incoming power supply should be brought into the panel via one of the knockouts
provided.
A suitable cable gland must be used to secure the outer sheath of the cable used.

Network Wiring

Panel-to-Repeater connections require 2 wires for a Legacy connection or 4 wires for a Fault
Tolerant connection and an additional 2 wires for 28v power.
The power connections for multiple repeaters should all be wired in parallel. The
communication connections should be wired from Com A to Com B on each link in the chain
of repeaters.
Each Repeater has a PCB-mounted DIL switch and must be allocated a unique address
between 9 and 16. Switch 4 must always be ON. Switches 1 to 3 represent a binary number
from 0 to 7 which allocates the corresponding address from 9 to 16.
Approved Document Ref: UI-ESA-03 Issue 2.0