Overload monitoring of
motors in the Ex e area
Adjusting the overload
current protection
j
2
Engineering
The Ex e protection of motors is achieved by means of
special design measures. The motors are assigned to
temperature classes on the basis of the highest permissible
surface temperatures. The temperature rise time t
ratio between starting current and rated operational current
I
/I
are calculated also and specified on the rating plate of
A
N
the motor.
The temperature rise time t
for the temperature of the motor winding to rise from its final
rated operational temperature up to the limit temperature,
at a starting current of I
However, Ex e motors are not safe on their own. Explosion
safety can only be achieved by taking additional measures
during installation and by selecting appropriate operational
conditions (PTB testing regulations), e.g. by adding a
correctly rated and set overload protection to the circuit.
Danger!
The selected current overload protection system must not
only ensure proper motor current monitoring, but also that
the seized motor is switched off within the temperature
rise time t
. This means that the protective device must be
E
rated so that the tripping time t
Ex e motor, that is specified by the characteristic curve, is
not greater than the temperature rise time t
switch off the motor safely within this time (
example).
represents the time that expires
E
t.
A
for the I
/I
A
A
a
and the
E
ratio of the
N
in order to
E
following
47