Stacked is not allowed for SMILE-G3-BAT-10.1P battery system

Barrier to habitable rooms

To protect against the spread of fire to habitable rooms, where the SMILE-BAT-G3-10.1P
is mounted on, placed against a surface of a wall or structure that has a habitable room on
the other side, the wall or structure shall be a suitably non-combustible barrier. If the
mounting surface itself is not made of a suitably non-combustible material, a non-
combustible barrier may be placed between the SMILE-BAT-G3-10.1P and the surface of
a wall or structure.
Where the SMILE-BAT-G3-10.1P is located on or within 300mm of the wall or structure
separating it from the habitable room, the barrier shall extend —
(i)
300 mm beyond the vertical sides of the SMILE-BAT-G3-10.1P;
(ii) to the extent of the bottom of the SMILE-BAT-G3-10.1P
Where the top of the SMILE-BAT-G3-10.1P is within 1200 mm of the ceiling or structure
above the SMILE-BAT-G3-10.1P the ceiling or structure surface shall be suitably non-
combustible for an area of 600 mm past the extremities of the SMILE-BAT-G3-10.1P.
SMILE-BAT-G3-10.1P shall be mounted with the highest point no greater than 2.2 m above
the floor or platform.
50℃
-10℃
IP65/Outdoor
90kg