Restricted Locations; Barrier To Habitable Rooms - Alpha ESS eSTORE-BAT-10.3 Manual

Battery module
Table of Contents

Advertisement

Your Smart Energy
places with flammable materials or gases or an explosive atmosphere.
places without clearance of right photo shows.
Restricted Locations
The battery system shall not be installed —
(a) in restricted locations, as defined for switchboards in AS/NZS 3000;
(b) within 600 mm of any hot source, such as water unit, gas heater, air conditioning unit
or any other appliance.
(c) within 600 mm of any exit;
(d) within 600 mm of any window or ventilation opening;
(e) within 900 mm of access to 240 Vac connections; and
(f) within 600 mm of side of other equipment.
An eSTORE-BAT-10.3 installed in any corridor, hallway, lobby or the like leading to a fire
exit shall ensure sufficient clearance from the ESTORE-BAT-10.3 for safe egress and no
less than 1 m.
An eSTORE-BAT-10.3 is considered a source of ignition and therefore shall not be installed
within hazardous area for gas cylinders containing heavier than air gasses and gas relief
vent terminal as defined in AS/NZS 3000.
Barrier to habitable rooms
To protect against the spread of fire to habitable rooms, where the eSTORE-BAT-10.3 is
mounted on, placed against a surface of a wall or structure that has a habitable room on
the other side, the wall or structure shall be a suitably non-combustible barrier. If the
mounting surface itself is not made of a suitably non-combustible material, a non-
combustible barrier may be placed between the M4856-P and the surface of a wall or
structure.
Where the eSTORE-BAT-10.3 is located on or within 300mm of the wall or structure
separating it from the habitable room, the barrier shall extend —
(i)
600 mm beyond the vertical sides of the ESTORE-BAT-10.3;
(ii) 1200 mm above the ESTORE-BAT-10.3; and
(iii) to the extent of the bottom of the ESTORE-BAT-10.3
Where the top of the ESTORE-BAT-10.3 is within 1200 mm of the ceiling or structure above
the ESTORE-BAT-10.3, the ceiling or structure surface shall be suitably non-combustible
for an area of 600 mm past the extremities of the ESTORE-BAT-10.3.
ESTORE-BAT-10.3 shall be mounted with the highest point no greater than 2.2 m above
______________________________________________________________________
Page 12 of 31