MAGNA3

2. Product range

Single-head pump models
MAGNA3 32-60 F (N)
MAGNA3 32-100 F (N)
MAGNA3 40-80 F (N)
MAGNA3 40-120 F (N)
MAGNA3 40-180 F (N)
MAGNA3 50-80 F (N)
MAGNA3 50-150 F (N)
MAGNA3 65-120 F (N)
MAGNA3 65-150 F (N)
MAGNA3 80-100 F (N)
MAGNA3 100-120 F (N)
Twin-head pump models
MAGNA3 D 65-150 F
MAGNA3 D 80-100 F
MAGNA3 D 100-120 F
Pump selection
All pumps have a "best point" (η
the pump is working most efficiently.
Consider the parameters in the following section.
Pump size
The system characteristic is used together with the
performance curve of the pump for sizing and correct
pump selection.
The selection of pump size must be based on the
following:
• required maximum flow
• maximum pressure loss in the system.
Refer to the system characteristics to determine the
duty point. See fig. 7.
H
System characteristic
Fig. 7
Cast iron
115 V
230 V
98126820
98126824
98126800
98126828
98126804
98126832
98126808
98126836
98126812
98126840
98126816
98126844
98124696
98126848
-
98126852
-
98126856
-
98126860
-
98126863
-
98126864
-
98126865
), indicating where
max
Duty point
Q
Stainless steel (N)
115 V
230 V
98126822
98126826
98126802
98126830
98126806
98126834
98126810
98126838
98126814
98126842
98126818
98126846
98124702
98126850
-
98126854
-
98126858
-
98126862
-
-
-
-
-
-
Operating conditions
You must check whether the operating conditions are
fulfilled, i.e:
• liquid quality and temperature
• ambient conditions
• minimum inlet pressure
• maximum operating pressure.
See also
conditions, page 32.
Operating
Closed valve operation
A MAGNA3 pump can operate at any speed against a
closed valve for several days without damage to the
pump. However, Grundfos recommends to operate at
the lowest possible speed curve to minimize energy
losses. There are no minimum flow requirements.
Note: Do not close inlet and outlet valves
simultaneously, always keep one open when the pump
is running. Media- and ambient temperatures must
never exceed the specified temperature range.
2
Page reference
43
44
45
46
47
48
49
50
51
53
55
52
54
56
7