4
Available CIM modules
Module
CIM 050
CIM 100
CIM 200
CIM 300
CIM 500
For product numbers, see
28
Fieldbus protocol
Description
CIM 050 is a Grundfos communication
GENIbus
interface module used for communication
with a GENIbus network.
CIM 100 is a Grundfos communication
LonWorks
interface module used for communication
with a LonWorks network.
CIM 200 is a Grundfos communication
Modbus RTU
interface module used for communication
with a Modbus RTU network.
CIM 300 is a Grundfos communication
BACnet MS/TP
interface module used for communication
with a BACnet MS/TP network.
CIM 500 is a Grundfos communication
interface module used for data
transmission between an industrial
Ethernet network and a Grundfos product.
CIM 500 supports various industrial
Ethernet
Ethernet protocols:
• PROFINET
• Modbus TCP
• BACnet/IP
• Ethernet/IP
modules, page 57.
CIM
MAGNA3
Functions
CIM 050 has terminals for the GENIbus
connection.
CIM 100 has terminals for the LonWorks
connection.
Two LEDs are used to indicate the actual status
of the CIM 100 communication.
One LED is used for indication of correct
connection to the pump, and the other is used to
indicate LonWorks communication status.
CIM 200 has terminals for the Modbus
connection.
DIP switches are used to select parity and stop
bits, to select transmission speed and to set line
termination.
Two hexadecimal rotary switches are used to set
the Modbus address.
Two LEDs are used to indicate the actual status
of the CIM 200 communication.
One LED is used for indication of correct
connection to the pump, and the other is used to
indicate Modbus communication status.
CIM 300 has terminals for the BACnet MS/TP
connection.
DIP switches are used to set transmission speed
and line termination and to select the custom
Device Object Instance Number.
Two hexadecimal rotary switches are used to set
the BACnet address.
Two LEDs are used to indicate the actual status
of the CIM 300 communication.
One LED is used for indication of correct
connection to the pump, and the other is used to
indicate BACnet communication status.
CIM 500 supports various industrial Ethernet
protocols. CIM 500 is configured via the built-in
web server, using a standard web browser on a
PC.
See the specific functional profile on the
DVD-ROM supplied with the Grundfos CIM
module.