4.0 TERMINATION LOCATION

4.1 Chimney Vent Termination Clearances

WARNING: This appliance must not share or be connected to a chimney
flue serving any other appliance.
Approved vent caps require 12" (305mm) clearance to
intersecting walls, overhangs or eaves as verified by test.
Figure 4.1, 3" x 3" Vent Cap Clearance through Existing Chimney

4.2 Co-linear to Co-axial Vent Terminations

WARNING: This appliance must not share or be connected to a chimney
flue serving any other appliance.
When combining co-linear and co-axial venting in a single venting
system using an approved 4" x 6-5/8" adapter, use Figure 4.2, Figure
4.3, and Table 4.1 for proper termination clearances.
Figure 4.2 Clearance between two Vertical Terminations
14
TERMINATION LOCATION
Figure 4.3, Co-linear to Co-axial Vertical Termination Clearances
T a b le 4 .1 , M in im u m V e r t ic a l T e r m in a t io n H e ig h t (u s e w it h F ig u r e 4 .3 )
Roof Pitch
Flat to 6/12
Over 6/12 to 7/12
Over 7/12 to 8/12
Over 8/12 to 9/12
Over 9/12 to 10/12
Over 10/12 to 11/12
Over 11/12 to 12/12
Over 12/12 to 14/12
Over 14/12 to 16/12
Over 16/12 to 18/12
Over 18/12 to 20/12
Over 20/12 to 21/12
Hussong Mfg. Co., Inc. Kozy Heat Fireplaces
Minimum height (H) from roof
Feet
Meters
1.0
0.30
1.25
0.38
1.5
0.46
2.0
0.61
2.5
0.76
3.25
0.99
4.0
1.22
5.0
1.52
6.0
1.83
7.0
2.13
7.5
2.27
8.0
2.44
#NDK-34-i R.1 July 2022