Orion RKS250F-S Operation Manual page 21

Unit cooler circulation-type liquid cooler
Table of Contents

Advertisement

Parameter Types and Functions
■ Parameter List (Settings can be changed while the product is running, except for "F15".)
Parameter
Number
F1
Power-cutoff recovery setting
Local / Remote operation priority
F2
enable / disable
F3
Warning signal output
F5
Audible alarm ON / OFF select
F6
Audible warning ON / OFF
F10
Parameter change lockout
F20
Liquid temp high / low warning enable
Liquid temp high / low warning relative
F21
value
Liquid temp high / low warning absolute
F22
upper limit value
Liquid temp high / low warning absolute
F23
lower limit value
500 Hr. filter replacement warning
F30
enable
F99
Setting lock
 
■ Parameter Function Details
● "F1" Blackout or power-cutoff recovery setting (relevant parameter "F2")
The product recovery pattern after a power outage can be selected.
"F1"
Description
Setting
0
Manual Recovery
1
Automatic Recovery
Remote operation switch
2
priority
※Factory default setting: 0.
< Setting restrictions >
"F1" setting will be according to the setting of "F2".
"F2" set value
0
1
Parameters
Parameter Types and Functions
Description
Operation status
before power outage
Product running
Stopped
Product running
Stopped
Product running
Stopped
Possible settings for "F1"
0, 1
2
0, 1, 2 
Setting
Units
range
0 ~ 2
0 ~ 2
0 , 1
0 , 1
0 , 1
0 ~ 4
1.0 ~ 5.0
F23+2 ~ 30
0 ~ F22−2
0 , 1
0 , 1
Operation status after
power recovery
All stopped
All stopped
Automatic product restart
All stopped
When remote is ON:
automatic product restart
When the remote switch is
OFF: all stopped
When remote is ON:
automatic product restart
When the remote switch is
OFF: all stopped
18
Min. set
Factory default
value
setting
1
0
1
2
1
0
1
1
1
1
0
1
0
0.1
5.0
0.1
30.0
0.1
5.0
1
1
1
0
Display after power
recovery
E14
None
None
None
None
None
None