Install the transparent PVC hose to the
4
pump discharge connection.
Pull the the transparent PVC tube to the
desired discharge place taking care not to
5
bend or pinch it. Secure it with Rilsan
clamps to prevent the weight of water from
distorting it.
Install the anti-siphoning device to the
rising part of the discharge tube after
6
cutting it and respecting the mounting rules
(see X.2.g Installation of the anti-siphoning
device here after).
Connect the electrical cable to the terminals
of the J6 connector (available near the
pump) in accordance with the wiring
7
diagram (see XVII GENERAL WIRING
DIAGRAM) and by removing the shunt
connected between terminals (3) and (4)
beforehand.
8
Plug the connector to the pump and lock it.
The transparent PVC tube must not pass through any area that may cause condensate to freeze.
X.2.g.
If the end of the discharge tube is below the condensate lift pump level, there is a risk of siphoning the pump which can lead to its
failure by repeated dry running. To avoid this, it is therefore necessary to install the anti-siphoning device supplied in the condensate
lift pump kit.
The anti-siphoning device keeps a sufficient column of water in the pump discharge tube when it stops. It must be installed at a
higher level than the pump, vertically or horizontally, taking care to be oriented to the following recommendations:
MS-CDF-019 – Manufacturing Nr: 220001→
Installation of the anti-siphoning device
EVERSKY
Terminal
Wire color
1
Blue
2
Brown
3
Grey
4
Black
Version B
Update: 2022/06/14
J6
1 2
3 4
J7
PRC
27/70