Xiv.12. Bacnet Ip Communication - Caladair EVERSKY 500 Installation And Commissioning Manual

Decentralised energy recovery unit
Table of Contents

Advertisement

The Modbus TCP protocol requires the following settings to be adjusted:
DHCP (Dynamic Host
Protocol)
IP
Subnet mask
Gateway
DNS
Device ID*
*The device ID is to be set according to the need of the BMS (recommended setting between 1 and 247) from the menu
Communication / Function port 1 / Communication Modbus (the device ID is shared between the RS485 port and the TCP-IP port).
XIV.12.
Bacnet IP Communication
If the IP Bacnet is enabled while the MS-TP Bacnet is also enabled, the MS-TP Bacnet will be automatically disabled, priority is given
to the IP Bacnet.
When IP Bacnet is enabled, TCP Modbus is automatically disabled since these two protocols share the same port.
The Bacnet IP protocol requires the following settings to be set:
DHCP (Dynamic Host
Protocol)
IP
Subnet Mask
Gateway
DNS
Device name
BBMD Adress
Device ID low
Device ID high (x 10000)
UDP port number low
UDP port number high (x 10000)
The list of read/write accessible variables is available in the chapter XXIV DATA EXCHANGE TABLES.
MS-CDF-019 – Manufacturing Nr: 220001→
Configuration
YES/NO
Example: 192.33.50.120
Example: 255.255.255.0
Example: 192.33.50.40
Example: 192.33.50.5
Setting the Modbus TCP protocol
CorrigoVentilation
Configuration
Example: 192.33.50.120
Example: 255.255.255.0
Example: 192.33.50.40
Example: 192.33.50.5
Bacnet IP protocol settings
CorrigoVentilation
2640
0
7808
4
EVERSKY
IP setting
When DHCP is enabled, IP settings are assigned
automatically when the device boots from the DHCP
server of the subnet. A dynamic IP address will then
be assigned to the device.
In case DHCP is not enabled, it is necessary to
manually
address/Netmask/Gateway/DNS).
Device name on the Bacnet IP network
IP Setting
When DHCP is enabled, IP settings are assigned
automatically when the device boots from the DHCP
server of the subnet. A dynamic IP address will then
be assigned to the device.
YES/NO
In case DHCP is not enabled, it is necessary to
manually
address/Netmask/Gateway/DNS).
Device name on the Bacnet IP network
The concatenation of the low ID and the top ID gives
the ID of the controller (000002640 i.e. 2640)
The concatenation of the low and high UDP port
number gives the UDP port number (47808)
assign
the
IP
assign
the
IP
Version B
Update: 2022/06/14
parameters
(IP
parameters
(IP
39/70

Advertisement

Table of Contents
loading

This manual is also suitable for:

Eversky 750Eversky 900Eversky 1100

Table of Contents