XXIV.3.
Alarm status (read-only)
Alarm presence
Supply air fan fault
Extract air fan fault
Supply / extract air filters fault
Internal battery fault
Electrical heating coil overheating
hot water heating coil frost protection
Fire mode active
It is not possible to acknowledge alarms (class A and B) via communication.
MS-CDF-019 – Manufacturing Nr: 220001→
EVERSKY
Modbus
Read
Write
Register Type
X
Input Status
X
Input Status
X
Input Status
X
Input Status
X
Input Status
X
Input Status
X
Input Status
X
Input Status
Version B
Modbus
Modbus
BACnet
Address
Variable
Address
30
bool
BV, 20030 0=no alarm / 1=at least one alarm is present
33
bool
BV, 20033 0=no alarm / 1=alarm presence
34
bool
BV, 20034 0=no alarm / 1=alarm presence
38
bool
BV, 20038 0=no alarm / 1=alarm presence
80
bool
BV, 20080 0=no alarm / 1=alarm presence
55
bool
BV, 20055
40
bool
BV, 20040
42
bool
BV, 20042 0=no alarm / 1=alarm presence
Update: 2022/06/14
67/70
Details
0=no alarm / 1=alarm presence
Only for units with electrical heating coil
0=no alarme / 1=alarm presence
Only for units with hot water heating coil