Table of Contents

Advertisement

Specification
Emissions sound-pressure level
Energy efficiency index (EEI)
Temperature class
Pollution degree
Max. permissible operating pressure
For further instructions see rating plate and catalogue.
Technical data Yonos MAXO-Z
Specification
Permissible fluid temperature
Permissible ambient temperature
Maximum relative humidity
Mains voltage
Residual current ∆I
Electromagnetic compatibility
Emissions sound-pressure level
Energy efficiency index (EEI)
Temperature class
Pollution degree
Max. permissible operating pressure
For further instructions see rating plate and catalogue.
5.4

Min. inlet pressure

Nominal diameter
G 1½
G 2
DN 32
DN 40
Installation and operating instructions • Wilo-Yonos MAXO/-D/-Z • Ed.01/2022-08
-20 °C to +50 °C
1)
0 °C to +50 °C
0.3 bar
0.3 bar
0.3 bar
0.5 bar
Value
< 52 dB(A)
See rating plate
TF110 (see IEC 60335-2-51)
2 (IEC 60664-1)
PN 6/10
Value
0 °C ... +80 °C (for short periods (2 h): +110 °C)
0 °C ... +40 °C
≤ 95 %
1~ 230 V +/-10 % 50/60 Hz
≤ 3.5 mA
Interference emission in acc. with:
EN 61800-3:2004+A1:2012/residential environment
(C1)
Interference immunity in acc. with:
EN 61800-3:2004+A1:2012/industrial environment
(C2)
< 52 dB(A)
See rating plate
TF80 (see IEC 60335-2-51)
2 (IEC 60664-1)
PN 6/10
Fluid temperature
up to +95 °C
1.0 bar
1.0 bar
1.0 bar
1.2 bar
en
up to +110 °C
1.6 bar
1.6 bar
1.6 bar
1.8 bar