If the ratio of the current transformer is either 2500:1 or 4000:1
The next table lists some burden resistor settings based on two types of current
transformers (2500:1 and 4000:1) and some values for the nominal current I
As long as the nominal current of the power stack is close to these cur-
rents and the current transformers are identical as listed below this op-
tion for coding the current should be used!
In such a case remove the jumpers on the SDCS-PIN-51 board according to the
current selected and set parameter S ConvScaleCur (97.02) to exactly that se-
lected rated current.
Current transf. ratio
Nominal current I
R1-R4
R5
R6
R7
R8
R9
R10
R11
R12
R13
R14
R15
R16
R17
R18
R19
R20
R21
R22
R23
R24
R25
R26
indicates a removed jumper
Hint:
In case a DCS800-R0x will be used to replace a DCR500B or DCR600 keep the
coding of the SDCS-PIN-51 board as done in the past and set parameter 97.02
exactly to that value the SDCS-PIN-51 board was coded.
The zero current detection is done on the controller board SDCS-CON-4. Because
of that the resistors available for that function need not to be coded!
Hardware
2500:1
[A]
900
1200
dN
18 Ω
18 Ω
18 Ω
18 Ω
18 Ω
18 Ω
18 Ω
18 Ω
18 Ω
18 Ω
18 Ω
18 Ω
18 Ω
33 Ω
68 Ω
120 Ω
270 Ω
560 Ω
47 Ω
47 Ω
47 Ω
47 Ω
100 Ω
3ADW000197R0101 DCS800-R Sel e a
1500
2000 2500
3000 2600
.
dN
4000:1
3300
4000
4800
5200
DCS800-R volt & curr coding.dsf