Touch Screen; Touch Screen Calibration - Maple Systems OMI6912A Operation Manual

Table of Contents

Advertisement

OMI Operations Manual: OMI6900 Series

TOUCH SCREEN

The OMI6900 Series includes an analog resistive touch screen. An application is pre-loaded onto your
OMI6900 Series which allows you to calibrate and change the settings of the touch screen.

Touch Screen Calibration

The touch screen may need to be recalibrated from time-to-time. There are two calibration methods:
'Standard Calibration' and 'Advanced Calibration':
Standard Calibration: The simpler of the two methods, this method can be used for most touch
screen calibrations required.
Advanced Calibration: As your OMI6900 ages, the touch screen may require finer adjustments
which can be accomplished using this method.
1. Click "Start", then "All Programs", and
select "PenMount Windows Universal
Driver (WHQL)".
Open the "Utility" folder and click
"PenMount Control Panel"
When the PenMount Control Panel
window opens, select "PenMount 6000
USB" and click "Configure".
2. Select "Standard Calibration" or
"Advanced Calibration".
"Turn off EEPROM storage"- this option
will disable writing any calibration data to
the EEPROM controller. Default is
enabled.
OMI Operations Manual: OMI6900 Series
28