The display °C (LED4) cannot be selected.
Signal output 1
Switch signal is the limit value for volume flow, hysteresis or window
function as NO or NC contact
Pulse sequence for consumption quantity with 1 pulse/standard litre
(pulse length 2 ms) and 1 pulse/Nm³ (pulse length 100 ms)
Signal output 2
Switch signal is the limit value for volume flow, hysteresis or window
function as NO or NC contact
Analog signal (4 - 20 mA) for corresponding volume flow
Pulse sequence for consumption quantity with 1 pulse/standard litre
(pulse length 2 ms) and 1 pulse/Nm³ (pulse length 100 ms)
Relative
meas.
range (%)
* Absolute measuring range depends on the nominal width (see following
table)
Compressed air counter
The compressed air counter may only be used for measuring the volume
flow of working compressed air with up to 16 bar positive pressure.
Nominal width
Meas. range*
DN 65
6,7 – 2000 m³/h
DN 80
9,2 – 2750 m³/h
DN 100
15 – 4440 m³/h
DN 125
23 – 7000 m³/h
DN 150
33 – 10,000 m³/h
DN 200
58 – 17,500 m³/h
DN 250
92 – 27,500 m³/h
*Specifications acc. to DIN ISO 2533 (15 °C, 1013 hPa and 0 % rel. hu-
midity)
When using the totaliser function (consumption meter m³), the display value
must be multiplied by 1000.
As of DN 150 the display range with 4-digit representation of the m³/h is in-
sufficient. The display value is to be multiplied by 1000.
Based on the small size, the sensor only has a small contact surface. The
pressure loss is thus negligible (typ. 1 mbar).
3 Description of the instrument
Measuring range
0,33% (0,4%) - 100%*
( ) : Value shown in display
Recording/display range
0 – 2400 m³/h
0 – 3300 m³/h
0 – 5320 m³/h
0 – 8400 m³/h
0 - 12.0 (x 1000) m³/h
0 - 21.0 (x 1000) m³/h
0 - 33.0 (x 1000) m³/h
Recording/display range
0% - 120%*
11