Electrical Cable Size; Pictographs - Atlas Copco MAS 200 Instruction Book

Table of Contents

Advertisement

Ref.
K22
K23
K34
Q1
T1/2
1X3
4.7

Electrical cable size

Cable size
Model
Motor
voltage
(V)
MAS 200
440
MAS 200
480
FLA*: Full-Load Ampacity
4.8

Pictographs

Control panel
50
Description
Star contactor
Delta contactor
Relay
Circuit breaker
Transformers
Terminal strip
All cables should be mounted on a horizontal ventilated (with spacing) tray.
Connect cables in the cubicle with the correct cable lugs.
Spacing of 10 mm between naked cable parts should be obtained.
Copper conductors with a 95 °C isolation class should be applied.
Fuse
selection (A)
2x (3x 250)
2x (3x 250
Pictographs of control panel
FLA*
Recommended
(A)
cable size (mm²)
365
2x (3x 120+70)
347
2x (3x 120+70)
Instruction book
Cable
Cable size
length
(mm²)
(m)
284
4x (3x 50+25)
310
4x (3x 50+25)
Cable
length (m)
147
160
APF219617

Advertisement

Table of Contents