Electric Cable Size And Fuses - Atlas Copco GA 18 VSD+ Instruction Book

Oil-injected rotary screw compressors
Table of Contents

Advertisement

Instruction book
9.2

Electric cable size and fuses

Important
Leakage breaker (optional)
If the installation requires a leakage breaker, always use an all current sensitive leakage breaker,
RCM or RCD Type B (according to IEC/EN 60755) with a sufficient trip level.
Currents and fuses
IEC approval
Compressor type
GA 18 VSD+
GA 18 VSD+
GA 18 VSD+
GA 18 VSD+
GA 18 VSD+
GA 18 VSD+
GA 18 VSD+
Compressor type
GA 22 VSD+
GA 22 VSD+
GA 22 VSD+
2920 7110 05
• The voltage on the compressor terminals must not deviate more than 10% of the
nominal voltage.
It is however highly recommended to keep the voltage drop over the supply cables
at nominal current below 5% of the nominal voltage (IEC 60204-1).
• If cables are grouped together with other power cables, it may be necessary to use
cables of a larger size than those calculated for the standard operating conditions.
• Use the original cable entry. See section
To preserve the IP protection degree of the electric cubicle and to protect its
components from dust from the environment, it is mandatory to use a proper
cable gland when connecting the supply cable to the compressor.
• Local regulations remain applicable if they are stricter than the values proposed
below.
• Caution:
• Always double-check the fuse size versus the calculated cable size. If
required, reduce fuse size or enlarge cable size.
• Cable length should not exceed the maximum length according to IEC60204
table 10.
V
Hz
200
50/60
230
50/60
380
60
400
50
400+N
50
460
60
500
50
V
Hz
200
50/60
230
50/60
380
60
Dimension
I
(1)
Maximum fuse (1) I
max
gL/gG
aR
A
A
A
88.1
100
-
88.8
100
-
44.5
-
50
44.1
50
44.1
50
44.4
50
35.2
40
-
I
(1)
Maximum fuse (1) I
max
gL/gG
aR
A
A
A
118.1
125
-
118.7
125
-
59.5
-
63
drawings.
(2)
Maximum fuse (2)
max
gL/gG
aR
A
A
A
94.2
100
-
94.9
100
-
49.1
-
50
48.6
-
50
48.6
-
50
49.0
50
37.7
40
-
(2)
Maximum fuse (2)
max
gL/gG
aR
A
A
A
124.3
125
-
125.0
125
-
64.2
-
80
103