Reference Sizing - Gardner Denver RNC Series Instruction Manual

Refrigerated type compressed air dryers
Hide thumbs Also See for RNC Series:
Table of Contents

Advertisement

5.0 REFERENCE
SIZING
Determining dryer capacity at actual operating conditions.
To determine the maximum inlet flow capacity of a dryer at vari-
ous operating conditions, multiply the rated capacity from Table
1 by the multipliers shown in Table 2.
Example: How many scfm can a 60 Hz air-cooled model 1000
handle when compressed air to be dried is at 200 psig and 100°F;
ambient air temperature is 80°F?
Answer: 1,000 x 1.22 x 1.12 = 1,366 scfm.
TABLE 1
Rated capacity (scfm) @ 100 psig inlet pressure, 100°F inlet
temperature, and 100°F ambient temperature.
MODEL
1000
1250
Rated capacity
60 Hz
1000
1250
of air-cooled
50 Hz
830
1050
models (scfm)
TABLE 2
Air capacity correction factors (Multipliers)
INLET COMPRESSED AIR CONDITIONS
INLET TEMPERATURES
INLET
PRESSURES
80°F
90°F
psig
barg
27°C
32°C
50
3.4
1.35
1.05
80
5.5
1.50
1.17
100
6.9
1.55
1.23
125
8.6
1.63
1.31
150
10.3
1.70
1.37
175
12.1
1.75
1.42
200
13.8
1.80
1.47
COOLING MEDIUM*
AMBIENT
TEMPERATURE
MULTIPLIER
°F
°C
80
27
1.12
90
32
1.06
100
38
1.00
110
43
0.94
*Air-cooled models; water-cooled models use 1.15 multiplier if cooling water is
below 95°F (35°C).
1500
1750
2000
2500
1500
1750
2000
2500
1250
1460
1670
2080
100°F
110°F
120°F
38°C
43°C
49°C
0.84
0.69
0.56
0.95
0.79
0.66
1.00
0.82
0.70
1.07
0.91
0.74
1.13
0.95
0.80
1.18
0.99
0.84
1.22
1.03
0.89
3000
3000
2500
17