Flow computer with temperature and pressure compensation for corrected gas volume, signal input flowmeter: pulse, namur and coil, signal input pressure: 0 4-20 ma, signal input temperature: pt100, 2 or 3- wire, signal outputs: 0 4-20ma / 0-10v ref. correc (64 pages)
Ratio monitor / totalizer with high / low alarms and analog outputs, signal input flowmeter: pulse, namur and coil, signal outputs: 4-20ma / 0-10v ref. ratio or flow rate, alarm outputs: up to three flow rate alarm outputs, options: intrinsically safe, mo (64 pages)
Page 1
F050-A PRESSURE INDICATOR Signal input sensor: (0)4-20mA Options: Intrinsically Safe F-Series - Field mounted indicators for safe and hazardous areas. More info: www.fluidwell.com/fseries...
The F050-A must be installed in accordance with the EMC guidelines (Electro Magnetic Compatibility). • Connect a proper grounding to the metal enclosure as indicated if the F050-A has an incoming power or signal line which carries a hazardous live voltage. The Protective Earth (PE) wire may never be disconnected or removed.
This operation manual describes the standard F050-A as well as most of the options available. For additional information, please contact your supplier. A hazardous situation may occur if the F050-A is not used for the purpose it was designed for or is used incorrectly. Please carefully note the information in this operating manual indicated by the pictograms: A "warning !"...
ABOUT THE MANUAL ........................3 WARRANTY AND TECHNICAL SUPPORT ..................3 CONTENTS MANUAL ......................... 4 INTRODUCTION ........................6 System description of the F050-A .................... 6 OPERATIONAL ........................7 General information ......................... 7 Control panel ..........................7 Operator information and functions ..................7 CONFIGURATION ........................
Page 5
5.3.2 Terminal 6 - Type PD: Sensor supply ................... 35 Configuration examples Intrinsically Safe applications ............36 5.4.1 F050-A-PX-XI-ZB - Ex ia IIC/IIIC ................... 36 5.4.2 F050-A-PD-XI-ZB - Ex ia IIC/IIIC ................... 36 5.4.3 F050-A-PL-XI-ZB - Ex ia IIC/IIIC ................... 37 MAINTENANCE ........................
This manual describes the unit with an analog (0)4-20mA input type from the sensor "-A version". Other versions are available to process 0-10V sensor signals. One sensor with a passive or active (0)4-20mA signal output can be connected to the F050-A. To power the sensor, several options are available.
Page 7 2 OPERATIONAL GENERAL INFORMATION This chapter describes the daily use of the F050-A. This instruction is meant for users / operators. • The F050-A may only be operated by personnel who are authorized and trained by the operator of the facility. All instructions in this manual are to be observed •...
As soon as the input value is 5% outside the calibrated measurement range, the piegraph starts flashing. Meanwhile, LO CURRENT or HI CURRENT will be displayed. • Alarm 01-03 When "alarm" is displayed, please consult Appendix B: problem solving. FW-F050-A-M_v0404_01_EN.docx...
Make sure that the unit is not being used for any application when altering the settings. 3.2.1 ENTERING SETUP-LEVEL Configuration of the F050-A is done at SETUP-level, which can be reached at all times while the F050-A remains fully operational. At SETUP-level the display will deactivate the indicator and...
The combination of the SELECT-key and CLEAR-key is used to select a negative value. When a value can also be entered as a negative number, pressing the SELECT- key and CLEAR-key simultaneously will toggle the ‘–‘ (minus) sign on and off. FW-F050-A-M_v0404_01_EN.docx...
Please keep a record of all settings for later reference. Use the control panel to return to OPERATE-level PROG-key In order to return to the operator level, press the PROG-key for three seconds. When no keys are pressed for 2 minutes, SETUP-level will be left automatically. FW-F050-A-M_v0404_01_EN.docx...
Page 12 CONFIGURATION SETTINGS All settings of the F050-A can be set via the control panel. The following paragraphs give a detailed description of each setting. 3.3.1 OVERVIEW FUNCTIONS SETUP LEVEL SETUP FUNCTIONS AND VARIABLES PRESSURE UNIT mbar - bar - PSI - mPA - PA - no unit...
If a LED backlight has been supplied, it can be turned on or off. BL. BRIGHTNESS The backlight brightness is adjustable. The following can be selected: (optional) 1 – 5 (where 1 is minimum and 5 is maximum brightness) FW-F050-A-M_v0404_01_EN.docx...
When used with the internal battery option, the user can expect reliable measurement over a long period of time. The F050-A has several smart power management functions to extend the battery life time significantly. Two of these functions are available.
This protection is disabled with value 0000 (zero). Up to and including 4 digits can be programmed, for example 1234. TAGNUMBER For identification of the F050-A and communication purposes, a unique tag number of maximum 7 digits can be entered. FW-F050-A-M_v0404_01_EN.docx...
Operating Manual before carrying out its instructions. • The F050-A may only be operated by personnel who are authorized and trained by the operator of the facility. All instructions in this manual are to be observed.
The F0-Series can be supplied as suitable for Safe Area or Hazardous Area. Suitability for Intrinsic Safety is indicated in the model code by Type XI (e.g. F050-A-XI). For Intrinsically Safe applications: Installation and identification labels are shown in chapter 5.
The serial number can be reviewed on the identification label or in SETUP-menu Others. The production date is either shown separately on the label or indicated by the first 4 digits of the serial number representing year and week number (YYWW). FW-F050-A-M_v0404_01_EN.docx...
Plastic enclosure: 1 Nm per screw Aluminum enclosure: 1 Nm per screw Aluminum w. extended back enclosure: 1 Nm per screw Stainless steel enclosure: 2 Nm per screw 5. The F-Series in now ready to be returned to service. FW-F050-A-M_v0404_01_EN.docx...
0.12" 0.12" M20 x 1,5 3x 1/2"NPT 25mm 25mm 15 15 M20 x 1,5 M20 x 1,5 4x M20 x 1,5 29.1 mm (1.15”) 115 mm (4.53”) 31 mm (1.22”) Fig. 9: Dimensions – Aluminum and stainless steel enclosures FW-F050-A-M_v0404_01_EN.docx...
Meter mount by using one of the openings Pipe mount by using the mounting plate in the bottom of the back cover. with the bracket and hose clamps (accessory). Panel mount by using only the front cover Fig. 11: Installation – Mounting configurations FW-F050-A-M_v0404_01_EN.docx...
General directions: • The F050-A that came with a power module type PM; 110V-230V AC or type PD/PF with an option OR (the relays can handle 110V-230V AC) shall be connected to the Protective Earth (PE) stud which is installed in the metal back panel.
Within the United States all field wiring must conform to the National Electric Code, NFPA 70, Article 501-4(b). All field wiring enters the F050-A through the bottom of the enclosure and connects to the circuit assembly inside the enclosure. Wiring is routed through cable glands. Please make sure to order the F050-A with the correct drilling pattern and thread (metal) or hole (plastic) sizes.
C22.2 No. 61010-1 / UL61010-1 / EN/IEC 61010-1. The F050-A can be powered from an external power supply. An internal power supply is also available in the form of a lithium battery. When both external and internal power supplies are available, the internal power supply is interrupted and will act as a backup supply.
4.6.1 TERMINALS 1-2: SENSOR INPUT The F050-A requires a (0)4-20mA sensor signal which will be processed 4 times a second with a 16 bits accuracy. The input is not isolated. The screen of the signal wire can be connected to the common ground terminal. See paragraph 4.5.3.
TERMINAL 4-5: POWER SUPPLY - TYPE PX (DEFAULT) AND PD (OPTION) To power the F050-A an internal battery can be used (type PB) and / or an external DC power supply of 8-30V DC (type PX) or 16-30V DC (type PD). Connect the "-" to terminal 4 and the "+" to terminal 5.
4.7.2 TERMINALS 5-7: SENSOR INPUT The F050-A requires a (0)4-20mA sensor signal which will be processed 4 times a second with a 16 bit accuracy. The input is not isolated. The screen of the signal wire can be connected to the common ground terminal. See paragraph 4.5.3.
The F0-Series can be supplied as suitable for Safe Area or Hazardous Area. Suitability for Intrinsic Safety is indicated in the model code by Type XI (e.g. F050-A-XI). If Type XI is not indicated your device is not suitable for Intrinsically Safe applications!
Ga, the indicator shall be installed so, that even in the event of rare incidents, an ignition source due to impact or friction sparks between the enclosure and iron/steel is excluded. FW-F050-A-M_v0404_01_EN.docx...
The cable parameters are determined by the parameters of the system into which the F0-Series General Purpose Indicators is connected. Only certified Intrinsically Safe Fluidwell battery type FW-LiBat-0xx may be used and replaced in hazardous area. The entity parameters for F0-Series General Purpose Indicators, model F0xx-A-XI, are as follows: Terminals 1 and 2 –...
Page 32
The cable parameters are determined by the parameters of the system into which the F0-Series General Purpose Indicators is connected. Only certified Intrinsically Safe Fluidwell battery type FW-LiBat-0xx may be used and replaced in hazardous area. The entity parameters for F0-Series General Purpose Indicators, model F0xx-A-PL-XI, are as follows: Terminals 1 and 2 –...
Ga, the indicator shall be installed so, that even in the event of rare incidents, an ignition source due to impact or friction sparks between the enclosure and iron/steel is excluded. • For EPL Da the ambient temperature Ta shall not exceed 50 °C. FW-F050-A-M_v0404_01_EN.docx...
(terminals 11 and 12) 30 V 0 mH 100 mA 6.1 nF = 0.75 W From the safety point of view the circuits shall be considered to be connected to earth. FW-F050-A-M_v0404_01_EN.docx...
5.3.1 POWER SUPPLY WIRING The F050-A can be powered from an external power supply. An internal power supply is also available in the form of a lithium battery. When both external and internal power supplies are available, the internal power supply is interrupted and will act as a backup supply. Note that the optional backlight only works with an external power supply.
Please note: Type PX may be used in combination with the battery (Type PC). PX will power the F050-A, the battery will be disabled automatically until the power is disconnected. Configuration example IIA - IIB and IIC application - F050-A-PD-XI-ZB 5.4.2...
Fig. 24: F050-A-PL-XI-ZB - Ex ia IIC/IIIC - Intrinsically Safe application. Sensor supply voltage not available in this example. Please note: Type PL may be used in combination with the battery (Type PC). PL will power the F050-A, the battery will be disabled automatically until the power is disconnected. FW-F050-A-M_v0404_01_EN.docx...
(above 90% annual mean). It is the users responsibility to take all precautions to dehumidify the internal atmosphere of the F050-A in such a way that no condensation will occur, for example by placing dry silica-gel sachet in the casing just before closing it.
Safe area applications – Type PB • Before replacing the battery, verify that the new battery is undamaged, in good condition and suitable for use in the unit. (Type: StdLiBAT021 - re-ordering nr. SPB02) Fig. 26: Marking Type PB battery: Safe area StdLiBAT021 (SPB02) FW-F050-A-M_v0404_01_EN.docx...
Dispose of batteries in accordance with the (inter)national, the manufacturer’s and the plant owner’s standards and regulations. • Batteries pose an environmental hazard. • Do not dispose of as general waste or incinerate. • Return used batteries to a recycling point. FW-F050-A-M_v0404_01_EN.docx...
Type HJ Drilling: 3x 22mm (0.87”). Type HK Flat bottom - no drilling. Operating temperature Safe area -40°C to +80°C (-40°F to +178°F). Intrinsically Safe -40°C to +70°C (-40°F to +158°F). For EPL Da: -40°C to +50°C (-40°F to +122°F) FW-F050-A-M_v0404_01_EN.docx...
Page 42
ANSI/UL 60079-0 FM Class 3610 ANSI/UL 60079-11 FM Class 3810 RoHS EN 50581 IEC 63000 IP & NEMA EN 60529 ANSI/IEC 60529 NEMA 250 Note: See the applicable Declaration of Conformity or product certificate for specific revisions and publication dates. FW-F050-A-M_v0404_01_EN.docx...
Page 43
Load impedance 3kOhm Relationship Linear. Operational Operator functions Displayed functions • pressure • measuring unit • piegraph 0-100%. Pressure Digits 5 1/2 digits. Unit mBar - Bar - PSI - mPA - PA - no unit. Decimals 0 - 5. FW-F050-A-M_v0404_01_EN.docx...
Page 44 PROBLEM SOLVING In this appendix, several problems are included that can occur when the F050-A is going to be installed or while it is in operation. Pressure displays "0 / zero" while a signal is available: Check: • SETUP 1.3: is the span correct? •...
A marking was affi ed 22. ei , anager Technology . .Bo 6 5 60 AA e hel he etherlands oltawe 5 66 A e hel he etherlands luidwell B is 001 certified b A ertification B eander 1051 6 Arnhem he etherlands. FW-F050-A-M_v0404_01_EN.docx...
Fig. 12: Protective Earth (PE) connections on metal enclosure Fig. 13: Switch position voltage selection (type PF and PM). Fig. 14: Overview of terminal connectors F050-A – type PB / PD / PL / PX Fig. 15: Terminal connections - Analog signal input.