Inspection; Cleaning - Baltimore Aircoil Company TrilliumSeries TRF Operation & Maintenance Manual

Adiabatic cooler
Table of Contents

Advertisement

Inspection

Conduct external inspection of the equipment. Check for leaks, corrosion, and any structural damage.
Conduct internal inspection of the equipment. Check for anything unusual such as structural or mechanical component
damage.
Inspect the pump(s), make-up valve(s), and drain valve. Remove any construction debris from inside the valves/sump.
Thoroughly inspect the fan(s) for any mechanical or physical damage.
Check that the float switches move freely.
Inspect the water distribution system.

Cleaning

Remove all dirt and debris from the fan guard(s).
Inspect and clean the water distribution system.
Clean all mechanical components, such as the fan and motor.
Flush the sump to remove any accumulated dirt and debris.
Remove, clean, and replace the sump strainers.
Flush the piping supply water to the unit for at least 5 minutes to remove flux shavings and other construction debris.
If necessary, clean the coil.
If necessary, clean the adiabatic pre-cooler pads.
After installation, remove any steel shavings from inside the unit. This will prevent shavings from rusting onto the surface
of the thermosetting hybrid polymer, which may affect the coating's integrity over extended time.
TrilliumSeries™ Adiabatic Cooler - TRF Operation & Maintenance Manual – Unit Operation & Storage
Page | 94