Bms Communication; Bacnet Ip & Modbus Tcp; Points List - Baltimore Aircoil Company TrilliumSeries TRF Operation & Maintenance Manual

Adiabatic cooler
Table of Contents

Advertisement

12. BMS Communication

BACnet IP & Modbus TCP
BACnet IP and Modbus TCP shall be connected via the RJ45 bulkhead at the bottom on the control panel.

Points List

Variable
Year
Month
Day
Hour
Minute
Second
LFT
LFTsetp
CtrlRange
AdiabaticSP
OAT
BMSrunEn
RunStatus
WaterDisable
FanSpdCmd
ActlFanSpd
ActlFanSpdRPM
TrilliumSeries™ Adiabatic Cooler - TRF Operation & Maintenance Manual – BMS Communication
Description
Current Year in YYYY format
Current Month in MM format
Current Day in DD format
Current Hour in HH format
Current Minute in MM format
Current Second in SS format
Leaving Fluid Temperature in x10
format [°C]
Leaving Fluid Temperature Setpoint
in x10 format [°C]
Control Range in x10 format [°C]
Adiabatic Switchpoint in x10 format
[°C]
Outside Air Temperature in x10
format [°C]
BMS Run Enable
0 = Off
1 = On
Trillium Run Status
0 = Not Running
1 = Running
Water Usage Disable. Forces the
unit into dry mode
0 = Water Usage Enabled
1 = Water Usage Disabled
Fan Speed Command in x10 format
[% max fan speed]
Average Fan Speed Feedback in
x10 format [%]
Average Fan Speed Feedback in
x10 format [RPM]
Data
Low
High
R/W
Type
Limit
Limit
R
A
R
A
R
A
R
A
R
A
R
A
R
A
W
A
4.4
50
W
A
0.5
5.5
W
A
5
50
R
A
W
B
R
B
W
B
R
A
R
A
R
A
Modbus
BACnet
RTU
Addresses
Registers
30001
AI1
30002
AI2
30003
AI3
30004
AI4
30005
AI5
30006
AI6
30007
AI7
42049
AV1
42050
AV2
42051
AV3
30008
AI8
2849
BV1
12401
BV2
2850
BV3
30009
AI9
30010
AI10
30011
AI11
Page | 107